RF Exposure

FCC ID: R7PNG0R1S2

RF Exposure Info

Download: PDF
FCCID_1890220

                   Certification Exhibit



                     FCC ID: R7PNG0R1S2
                      IC: 5294A-NG0R1S2

              FCC Rule Part: 15.247
    IC Radio Standards Specification: RSS-210

               ACS Project Number: 12-0182

      Manufacturer: Landis+Gyr Technology, Inc.
      Model: Gridstream S4 Modular SCADA/DA




                         RF Exposure




5015 B.U. Bowman Drive Buford, GA 30518 USA Voice: 770-831-8048 Fax: 770-831-8598


Model: Gridstream S4 Modular SCADA/DA                FCC ID: R7PNG0R1S2             IC: 5294A-NG0R1S2


General Information:
Applicant:           Landis+Gyr Technology, Inc.
Device Category:     Mobile
Environment:         General Population/Uncontrolled Exposure

Technical Information – External Antenna:
Antenna Type: Whip
Antenna Gain: 5dBi
Maximum Transmitter Conducted Power: 29.06 dBm, 805.378 mW
Maximum System EIRP: 34.06 dBm, 2546.83 mW
Exposure Conditions: Greater than 20 centimeters

Technical Information – Internal Antenna:
Antenna Type: F-Antenna
Antenna Gain: 0dB
Maximum Transmitter Conducted Power: 29.06 dBm, 805.378 mW
Maximum System EIRP: 29.06 dBm, 805.378 mW
Exposure Conditions: Greater than 20 centimeters

MPE Calculation
                        2
The Power Density (mW/cm ) is calculated as follows:

      PG
S=
     4πR 2
Where:
S = power density (in appropriate units, e.g. mW/cm2)
P = power input to the antenna (in appropriate units, e.g., mW)
G = power gain of the antenna in the direction of interest relative to an isotropic radiator
R = distance to the center of radiation of the antenna (appropriate units, e.g., cm)

                                MPE Calculator for Mobile Equipment
                       Limits for General Population/Uncontrolled Exposure*
  Transmit      Radio         Power        Radio    Antenna Antenna                         Power
                                                                       Distance
 Frequency      Power Density Limit        Power      Gain      Gain                        Density
                                                                         (cm)
   (MHz)        (dBm)      (mW/Cm2)        (mW)       (dBi)   (mW eq.)                    (mW/cm^2)
    915          29.06          0.61       805.38       5       3.162     20                 0.507

                                MPE Calculator for Mobile Equipment
                       Limits for General Population/Uncontrolled Exposure*
  Transmit      Radio         Power        Radio    Antenna Antenna                         Power
                                                                       Distance
 Frequency      Power Density Limit        Power      Gain      Gain                        Density
                                                                         (cm)
   (MHz)        (dBm)      (mW/Cm2)        (mW)       (dBi)   (mW eq.)                    (mW/cm^2)
    915          29.06          0.61       805.38       0       1.000     20                 0.160

Installation Guidelines
The installation manual should contain text similar to the following advising how to install the equipment to
maintain compliance with the FCC RF exposure requirements:
RF Exposure
In accordance with FCC requirements of human exposure to radio frequency fields, the radiating element
shall be installed such that a minimum separation distance of 20 centimeters will be maintained.
Conclusion
This device complies with the MPE requirements by providing adequate separation between the device,
any radiating structure and the general population.


     ACS Project: 12-0182                 Advanced Compliance Solutions                         Page 2



Document Created: 2013-01-30 10:37:48
Document Modified: 2013-01-30 10:37:48

© 2024 FCC.report