Attachment RadHaz

This document pretains to SES-MOD-20140331-00200 for Modification on a Satellite Earth Station filing.

IBFS_SESMOD2014033100200_1040332

                                                                                  Exhibit
Radiation Hazard Report                                                           Page 1 of 25


    Analysis of Non-Ionizing Radiation for a Winegard (SF840)
                 0.84-Meter Earth Station System
This report analyzes the non-ionizing radiation levels for a 0.84-meter earth station system. The
analysis and calculations performed in this report comply with the methods described in the FCC
Office of Engineering and Technology Bulletin, No. 65 first published in 1985 and revised in 1997
in Edition 97-01. The radiation safety limits used in the analysis are in conformance with the FCC
R&O 96-326. Bulletin No. 65 and the FCC R&O specifies that there are two separate tiers of
exposure limits that are dependant on the situation in which the exposure takes place and/or the
status of the individuals who are subject to the exposure. The Maximum Permissible Exposure
(MPE) limits for persons in a General Population/Uncontrolled environment are shown in Table 1.
The General Population/Uncontrolled MPE is a function of transmit frequency and is for an
exposure period of thirty minutes or less. The MPE limits for persons in an
Occupational/Controlled environment are shown in Table 2. The Occupational MPE is a function of
transmit frequency and is for an exposure period of six minutes or less. The purpose of the
analysis described in this report is to determine the power flux density levels of the earth station in
the far-field, near-field, transition region, between the subreflector or feed and main reflector
surface, at the main reflector surface, and between the antenna edge and the ground and to
compare these levels to the specified MPEs.

               Table 1. Limits for General Population/Uncontrolled Exposure (MPE)
                  Frequency Range (MHz)          Power Density (mW/cm2)
                          30-300                              0.2
                         300-1500                  Frequency (MHz)*(0.8/1200)
                       1500-100,000                           1.0

                    Table 2. Limits for Occupational/Controlled Exposure (MPE)
                  Frequency Range (MHz)          Power Density (mW/cm2)
                          30-300                              1.0
                         300-1500                  Frequency (MHz)*(4.0/1200)
                       1500-100,000                           5.0

          Table 3. Formulas and Parameters Used for Determining Power Flux Densities
     Parameter                    Symbol           Formula                 Value            Units
     Antenna Diameter                D               Input                  0.84            m
     Antenna Surface Area          Asurface         π D2 / 4                0.55            m2
     Subreflector Diameter          Dsr              Input                  19.0            cm
     Area of Subreflector           Asr             π Dsr 2/4              283.53           cm2
     Frequency                       F               Input                 14250            MHz
     Wavelength                      λ              300 / F              0.021053           m
     Transmit Power                  P               Input                  5.00            W
     Antenna Gain (dBi)             Ges              Input                  40.3            dBi
     Antenna Gain (factor)           G              10Ges/10              10715.2           n/a
     Pi                              π             Constant              3.1415927          n/a
     Antenna Efficiency              η             Gλ2/(π2D2)               0.68            n/a


                                                                                  Exhibit
Radiation Hazard Report                                                           Page 2 of 25




1. Far Field Distance Calculation

The distance to the beginning of the far field can be determined from the following equation:

   Distance to the Far Field Region                         Rff = 0.60 D2 / λ                    (1)
                                                                = 20.1 m

The maximum main beam power density in the far field can be determined from the following
equation:

   On-Axis Power Density in the Far Field                   Sff = G P / (4 π Rff 2)              (2)
                                                                = 10.543 W/m2
                                                                = 1.054 mW/cm2

2. Near Field Calculation

Power flux density is considered to be at a maximum value throughout the entire length of the
defined Near Field region. The region is contained within a cylindrical volume having the same
diameter as the antenna. Past the boundary of the Near Field region, the power density from the
antenna decreases linearly with respect to increasing distance.

The distance to the end of the Near Field can be determined from the following equation:

   Extent of the Near Field                                 Rnf = D2 / (4 λ)                     (3)
                                                                = 8.4 m

The maximum power density in the Near Field can be determined from the following equation:

   Near Field Power Density                                 Snf = 16.0 η P / (π D2)              (4)
                                                                = 24.611 W/m2
                                                                = 2.461 mW/cm2

3. Transition Region Calculation

The Transition region is located between the Near and Far Field regions. The power density
begins to decrease linearly with increasing distance in the Transition region. While the power
density decreases inversely with distance in the Transition region, the power density decreases
inversely with the square of the distance in the Far Field region. The maximum power density in
the Transition region will not exceed that calculated for the Near Field region. The power density
calculated in Section 1 is the highest power density the antenna can produce in any of the regions
away from the antenna. The power density at a distance Rt can be determined from the following
equation:

   Transition Region Power Density                          St = Snf Rnf / Rt                    (5)
                                                               = 2.461 mW/cm2


                                                                              Exhibit
Radiation Hazard Report                                                       Page 3 of 25

Region between the Main Reflector and the Subreflector

Transmissions from the feed assembly are directed     toward the subreflector surface, and are
reflected back toward the main reflector. The most    common feed assemblies are waveguide
flanges, horns or subreflectors. The energy between   the subreflector and the reflector surfaces
can be calculated by determining the power density    at the subreflector surface. This can be
determined from the following equation:

   Power Density at the Subreflector                      Ssr = 4000 P / Asr                 (6)
                                                              = 70.540 mW/cm2

4. Main Reflector Region

The power density in the main reflector is determined in the same manner as the power density at
the subreflector. The area is now the area of the main reflector aperture and can be determined
from the following equation:

   Power Density at the Main Reflector Surface        Ssurface = 4 P / Asurface              (7)
                                                               = 36.090 W/m2
                                                               = 3.609 mW/cm2


5. Region between the Main Reflector and the Ground

Assuming uniform illumination of the reflector surface, the power density between the antenna and
the ground can be determined from the following equation:

   Power Density between Reflector and Ground             Sg = P / Asurface                  (8)
                                                             = 9.022 W/m2
                                                             = 0.902 mW/cm2


                                                                                 Exhibit
Radiation Hazard Report                                                          Page 4 of 25

6. Summary of Calculations

           Table 4. Summary of Expected Radiation levels for Uncontrolled Environment
                                            Calculated Maximum
                                       Radiation Power Density Level
Region                                              (mW/cm2)               Hazard Assessment
1. Far Field (Rff = 20.1 m)                     Sff        1.054             Potential Hazard
2. Near Field (Rnf = 8.4 m)                     Snf        2.461             Potential Hazard
3. Transition Region (Rnf < Rt < Rff)           St         2.461              Potential Hazard
4. Between Main Reflector and                   Ssr       70.540             Potential Hazard
    Subreflector
5. Main Reflector                               Ssurface   3.609              Potential Hazard
6. Between Main Reflector and Ground            Sg         0.902            Satisfies FCC MPE

            Table 5. Summary of Expected Radiation levels for Controlled Environment
                                           Calculated Maximum
                                          Radiation Power Density
Region                                        Level (mW/cm2)               Hazard Assessment
1. Far Field (Rff = 20.1 m)                    Sff         1.054            Satisfies FCC MPE
2. Near Field (Rnf = 8.4 m)                    Snf         2.461            Satisfies FCC MPE
3. Transition Region (Rnf < Rt < Rff)          St          2.461            Satisfies FCC MPE
4. Between Main Reflector and                  Ssr       70.540              Potential Hazard
    Subreflector
5. Main Reflector                              Ssurface    3.609            Satisfies FCC MPE
6. Between Main Reflector and Ground           Sg          0.902            Satisfies FCC MPE

It is the applicant's responsibility to ensure that the public and operational personnel are not
exposed to harmful levels of radiation.



7. Conclusions

Based on the above analysis it is concluded that the FCC MPE guidelines have been exceeded (or
met) in the regions of Table 4 and 5. The applicant proposes to comply with the MPE limits by one
or more of the following methods.

The earth station will be located in an area with secured access. All individuals having access to
the antenna will be aware of the Radiation Hazard from the antenna, thus creating a controlled
environment. Warning signs will be in the area to warn individuals of the potential for radiation
hazard.

Finally, occupational exposure will be limited, and the transmitter will be turned off during periods
of maintenance, so that the MPE standard of 5.0 mw/cm**2 will be complied with for those regions
in close proximity to the main reflector, and subreflector, which could be occupied by operating
personnel.


                                                                                        Exhibit
Radiation Hazard Report                                                                 Page 5 of 25




                         bide by the conditions specified in Condition 5208 provided below:
The applicant agrees to abide

        Condition 5208 - The licensee shall take all necessary measures to ensure that the
        antenna does not create potential exposure of humans to radiofrequency radiation
        in excess of the FCC exposure
                                 osure limits defined in 47 CFR 1.1307(b) and 1.1310
        wherever such exposures might occur. Measures must be taken to ensure
        compliance with limits for both occupational/controlled exposure and for general
        population/uncontrolled exposure, as defined in these rule sections. Compliance
        can be accomplished in most cases by appropriate restrictions such as fencing.
        Requirements for restrictions can be determined by predictions based on
        calculations, modeling or by field measurements. The FCC's OET Bulletin 65
        (available on-line
                       line at www.fcc.gov/oet/rfsafety) provides information on predicting
        exposure levels and on methods for ensuring compliance, including the use of
        warning and alerting signs and protective equipment for worker.




I HEREBY CERTIFY THAT I AM THE TECHNICALLY QUALIFIED PERSON RESPONSIBLE FOR THE
PREPARATION OF THE RADIATION HAZARD REPORT, AND THAT IT IS COMPLETE AND CORRECT
TO THE BEST OF MY KNOWLEDGE AND BELIEF.




BY: _

Gary K. Edwards
Senior Manager
COMSEARCH
19700 Janelia Farm Boulevard
Ashburn, VA 20147


DATED: March 28, 2014


                                                                                  Exhibit
Radiation Hazard Report                                                           Page 6 of 25

  Analysis of Non-Ionizing Radiation for a Winegard (WX1200)
                1.2-Meter Earth Station System
This report analyzes the non-ionizing radiation levels for a 1.2-meter earth station system. The
analysis and calculations performed in this report comply with the methods described in the FCC
Office of Engineering and Technology Bulletin, No. 65 first published in 1985 and revised in 1997
in Edition 97-01. The radiation safety limits used in the analysis are in conformance with the FCC
R&O 96-326. Bulletin No. 65 and the FCC R&O specifies that there are two separate tiers of
exposure limits that are dependant on the situation in which the exposure takes place and/or the
status of the individuals who are subject to the exposure. The Maximum Permissible Exposure
(MPE) limits for persons in a General Population/Uncontrolled environment are shown in Table 1.
The General Population/Uncontrolled MPE is a function of transmit frequency and is for an
exposure period of thirty minutes or less. The MPE limits for persons in an
Occupational/Controlled environment are shown in Table 2. The Occupational MPE is a function of
transmit frequency and is for an exposure period of six minutes or less. The purpose of the
analysis described in this report is to determine the power flux density levels of the earth station in
the far-field, near-field, transition region, between the subreflector or feed and main reflector
surface, at the main reflector surface, and between the antenna edge and the ground and to
compare these levels to the specified MPEs.

               Table 1. Limits for General Population/Uncontrolled Exposure (MPE)
                  Frequency Range (MHz)          Power Density (mW/cm2)
                          30-300                              0.2
                         300-1500                  Frequency (MHz)*(0.8/1200)
                       1500-100,000                           1.0

                    Table 2. Limits for Occupational/Controlled Exposure (MPE)
                  Frequency Range (MHz)          Power Density (mW/cm2)
                          30-300                              1.0
                         300-1500                  Frequency (MHz)*(4.0/1200)
                       1500-100,000                           5.0

          Table 3. Formulas and Parameters Used for Determining Power Flux Densities
     Parameter                    Symbol           Formula                 Value            Units
     Antenna Diameter                D               Input                   1.2            m
     Antenna Surface Area          Asurface         π D2 / 4                1.13            m2
     Subreflector Diameter          Dsr              Input                  19.0            cm
     Area of Subreflector           Asr             π Dsr 2/4              283.53           cm2
     Frequency                       F               Input                 14250            MHz
     Wavelength                      λ              300 / F              0.021053           m
     Transmit Power                  P               Input                  5.00            W
     Antenna Gain (dBi)             Ges              Input                  43.0            dBi
     Antenna Gain (factor)           G              10Ges/10              19952.6           n/a
     Pi                              π             Constant              3.1415927          n/a
     Antenna Efficiency              η             Gλ2/(π2D2)               0.62            n/a


                                                                                  Exhibit
Radiation Hazard Report                                                           Page 7 of 25



8. Far Field Distance Calculation

The distance to the beginning of the far field can be determined from the following equation:

   Distance to the Far Field Region                         Rff = 0.60 D2 / λ                    (1)
                                                                = 41.0 m

The maximum main beam power density in the far field can be determined from the following
equation:

   On-Axis Power Density in the Far Field                   Sff = G P / (4 π Rff 2)              (2)
                                                                = 4.714 W/m2
                                                                = 0.471 mW/cm2

9. Near Field Calculation

Power flux density is considered to be at a maximum value throughout the entire length of the
defined Near Field region. The region is contained within a cylindrical volume having the same
diameter as the antenna. Past the boundary of the Near Field region, the power density from the
antenna decreases linearly with respect to increasing distance.

The distance to the end of the Near Field can be determined from the following equation:

   Extent of the Near Field                                 Rnf = D2 / (4 λ)                     (3)
                                                                = 17.1 m

The maximum power density in the Near Field can be determined from the following equation:

   Near Field Power Density                                 Snf = 16.0 η P / (π D2)              (4)
                                                                = 11.003 W/m2
                                                                = 1.100 mW/cm2

10.    Transition Region Calculation

The Transition region is located between the Near and Far Field regions. The power density
begins to decrease linearly with increasing distance in the Transition region. While the power
density decreases inversely with distance in the Transition region, the power density decreases
inversely with the square of the distance in the Far Field region. The maximum power density in
the Transition region will not exceed that calculated for the Near Field region. The power density
calculated in Section 1 is the highest power density the antenna can produce in any of the regions
away from the antenna. The power density at a distance Rt can be determined from the following
equation:

   Transition Region Power Density                          St = Snf Rnf / Rt                    (5)
                                                               = 1.100 mW/cm2


                                                                              Exhibit
Radiation Hazard Report                                                       Page 8 of 25

11.    Region between the Main Reflector and the Subreflector

Transmissions from the feed assembly are directed     toward the subreflector surface, and are
reflected back toward the main reflector. The most    common feed assemblies are waveguide
flanges, horns or subreflectors. The energy between   the subreflector and the reflector surfaces
can be calculated by determining the power density    at the subreflector surface. This can be
determined from the following equation:

   Power Density at the Subreflector                      Ssr = 4000 P / Asr                 (6)
                                                              = 70.540 mW/cm2

12.    Main Reflector Region

The power density in the main reflector is determined in the same manner as the power density at
the subreflector. The area is now the area of the main reflector aperture and can be determined
from the following equation:

   Power Density at the Main Reflector Surface        Ssurface = 4 P / Asurface              (7)
                                                               = 17.684 W/m2
                                                               = 1.768 mW/cm2


13.    Region between the Main Reflector and the Ground

Assuming uniform illumination of the reflector surface, the power density between the antenna and
the ground can be determined from the following equation:

   Power Density between Reflector and Ground             Sg = P / Asurface                  (8)
                                                             = 4.421 W/m2
                                                             = 0.442 mW/cm2


                                                                                 Exhibit
Radiation Hazard Report                                                          Page 9 of 25

14.    Summary of Calculations

           Table 4. Summary of Expected Radiation levels for Uncontrolled Environment
                                            Calculated Maximum
                                       Radiation Power Density Level
Region                                              (mW/cm2)               Hazard Assessment
1. Far Field (Rff = 41.0 m)                     Sff        0.471            Satisfies FCC MPE
2. Near Field (Rnf = 17.1 m)                    Snf        1.100             Potential Hazard
3. Transition Region (Rnf < Rt < Rff)           St         1.100              Potential Hazard
4. Between Main Reflector and                   Ssr       70.540             Potential Hazard
    Subreflector
5. Main Reflector                               Ssurface   1.768              Potential Hazard
6. Between Main Reflector and Ground            Sg         0.442            Satisfies FCC MPE

            Table 5. Summary of Expected Radiation levels for Controlled Environment
                                           Calculated Maximum
                                          Radiation Power Density
Region                                        Level (mW/cm2)               Hazard Assessment
1. Far Field (Rff = 41.0 m)                    Sff         0.471            Satisfies FCC MPE
2. Near Field (Rnf = 17.1 m)                   Snf         1.100            Satisfies FCC MPE
3. Transition Region (Rnf < Rt < Rff)          St          1.100            Satisfies FCC MPE
4. Between Main Reflector and                  Ssr       70.540              Potential Hazard
    Subreflector
5. Main Reflector                              Ssurface    1.768            Satisfies FCC MPE
6. Between Main Reflector and Ground           Sg          0.442            Satisfies FCC MPE

It is the applicant's responsibility to ensure that the public and operational personnel are not
exposed to harmful levels of radiation.



15.    Conclusions

Based on the above analysis it is concluded that the FCC MPE guidelines have been exceeded (or
met) in the regions of Table 4 and 5. The applicant proposes to comply with the MPE limits by one
or more of the following methods.

The earth station will be located in an area with secured access. All individuals having access to
the antenna will be aware of the Radiation Hazard from the antenna, thus creating a controlled
environment. Warning signs will be in the area to warn individuals of the potential for radiation
hazard.

Finally, occupational exposure will be limited, and the transmitter will be turned off during periods
of maintenance, so that the MPE standard of 5.0 mw/cm**2 will be complied with for those regions
in close proximity to the main reflector, and subreflector, which could be occupied by operating
personnel.


                                                                                        Exhibit
Radiation Hazard Report                                                                 Page 10 of 25




                         bide by the conditions specified in Condition 5208 provided below:
The applicant agrees to abide

        Condition 5208 - The licensee shall take all necessary measures to ensure that the
        antenna does not create potential exposure of humans to radiofrequency radiation
        in excess of the FCC exposure
                                 osure limits defined in 47 CFR 1.1307(b) and 1.1310
        wherever such exposures might occur. Measures must be taken to ensure
        compliance with limits for both occupational/controlled exposure and for general
        population/uncontrolled exposure, as defined in these rule sections. Compliance
        can be accomplished in most cases by appropriate restrictions such as fencing.
        Requirements for restrictions can be determined by predictions based on
        calculations, modeling or by field measurements. The FCC's OET Bulletin 65
        (available on-line
                       line at www.fcc.gov/oet/rfsafety) provides information on predicting
        exposure levels and on methods for ensuring compliance, including the use of
        warning and alerting signs and protective equipment for worker.




I HEREBY CERTIFY THAT I AM THE TECHNICALLY QUALIFIED PERSON RESPONSIBLE FOR THE
PREPARATION OF THE RADIATION HAZARD REPORT, AND THAT IT IS COMPLETE AND CORRECT
TO THE BEST OF MY KNOWLEDGE AND BELIEF.




BY: _

Gary K. Edwards
Senior Manager
COMSEARCH
19700 Janelia Farm Boulevard
Ashburn, VA 20147


DATED: March 28, 2014


                                                                                  Exhibit
Radiation Hazard Report                                                           Page 11 of 25

Analysis of Non-Ionizing Radiation for a Seatel (4006) 1.0-Meter
                     Earth Station System
This report analyzes the non-ionizing radiation levels for a 1.0-meter earth station system. The
analysis and calculations performed in this report comply with the methods described in the FCC
Office of Engineering and Technology Bulletin, No. 65 first published in 1985 and revised in 1997
in Edition 97-01. The radiation safety limits used in the analysis are in conformance with the FCC
R&O 96-326. Bulletin No. 65 and the FCC R&O specifies that there are two separate tiers of
exposure limits that are dependant on the situation in which the exposure takes place and/or the
status of the individuals who are subject to the exposure. The Maximum Permissible Exposure
(MPE) limits for persons in a General Population/Uncontrolled environment are shown in Table 1.
The General Population/Uncontrolled MPE is a function of transmit frequency and is for an
exposure period of thirty minutes or less. The MPE limits for persons in an
Occupational/Controlled environment are shown in Table 2. The Occupational MPE is a function of
transmit frequency and is for an exposure period of six minutes or less. The purpose of the
analysis described in this report is to determine the power flux density levels of the earth station in
the far-field, near-field, transition region, between the subreflector or feed and main reflector
surface, at the main reflector surface, and between the antenna edge and the ground and to
compare these levels to the specified MPEs.

               Table 1. Limits for General Population/Uncontrolled Exposure (MPE)
                  Frequency Range (MHz)          Power Density (mW/cm2)
                          30-300                              0.2
                         300-1500                  Frequency (MHz)*(0.8/1200)
                       1500-100,000                           1.0

                    Table 2. Limits for Occupational/Controlled Exposure (MPE)
                  Frequency Range (MHz)          Power Density (mW/cm2)
                          30-300                              1.0
                         300-1500                  Frequency (MHz)*(4.0/1200)
                       1500-100,000                           5.0

          Table 3. Formulas and Parameters Used for Determining Power Flux Densities
     Parameter                    Symbol           Formula                 Value            Units
     Antenna Diameter                D               Input                   1.0            m
     Antenna Surface Area          Asurface         π D2 / 4                0.79            m2
     Subreflector Diameter          Dsr              Input                  19.0            cm
     Area of Subreflector           Asr             π Dsr 2/4              283.53           cm2
     Frequency                       F               Input                 14250            MHz
     Wavelength                      λ              300 / F              0.021053           m
     Transmit Power                  P               Input                  5.00            W
     Antenna Gain (dBi)             Ges              Input                  41.8            dBi
     Antenna Gain (factor)           G              10Ges/10              15135.6           n/a
     Pi                              π             Constant              3.1415927          n/a
     Antenna Efficiency              η             Gλ2/(π2D2)               0.68            n/a


                                                                                  Exhibit
Radiation Hazard Report                                                           Page 12 of 25



16.    Far Field Distance Calculation

The distance to the beginning of the far field can be determined from the following equation:

   Distance to the Far Field Region                         Rff = 0.60 D2 / λ                     (1)
                                                                = 28.5 m

The maximum main beam power density in the far field can be determined from the following
equation:

   On-Axis Power Density in the Far Field                   Sff = G P / (4 π Rff 2)               (2)
                                                                = 7.414 W/m2
                                                                = 0.741 mW/cm2

17.    Near Field Calculation

Power flux density is considered to be at a maximum value throughout the entire length of the
defined Near Field region. The region is contained within a cylindrical volume having the same
diameter as the antenna. Past the boundary of the Near Field region, the power density from the
antenna decreases linearly with respect to increasing distance.

The distance to the end of the Near Field can be determined from the following equation:

   Extent of the Near Field                                 Rnf = D2 / (4 λ)                      (3)
                                                                = 11.9 m

The maximum power density in the Near Field can be determined from the following equation:

   Near Field Power Density                                 Snf = 16.0 η P / (π D2)               (4)
                                                                = 17.308 W/m2
                                                                = 1.731 mW/cm2

18.    Transition Region Calculation

The Transition region is located between the Near and Far Field regions. The power density
begins to decrease linearly with increasing distance in the Transition region. While the power
density decreases inversely with distance in the Transition region, the power density decreases
inversely with the square of the distance in the Far Field region. The maximum power density in
the Transition region will not exceed that calculated for the Near Field region. The power density
calculated in Section 1 is the highest power density the antenna can produce in any of the regions
away from the antenna. The power density at a distance Rt can be determined from the following
equation:

   Transition Region Power Density                          St = Snf Rnf / Rt                     (5)
                                                               = 1.731 mW/cm2


                                                                              Exhibit
Radiation Hazard Report                                                       Page 13 of 25

Region between the Main Reflector and the Subreflector

Transmissions from the feed assembly are directed     toward the subreflector surface, and are
reflected back toward the main reflector. The most    common feed assemblies are waveguide
flanges, horns or subreflectors. The energy between   the subreflector and the reflector surfaces
can be calculated by determining the power density    at the subreflector surface. This can be
determined from the following equation:

   Power Density at the Subreflector                      Ssr = 4000 P / Asr                  (6)
                                                              = 70.540 mW/cm2

19.    Main Reflector Region

The power density in the main reflector is determined in the same manner as the power density at
the subreflector. The area is now the area of the main reflector aperture and can be determined
from the following equation:

   Power Density at the Main Reflector Surface        Ssurface = 4 P / Asurface               (7)
                                                               = 25.465 W/m2
                                                               = 2.546 mW/cm2


20.    Region between the Main Reflector and the Ground

Assuming uniform illumination of the reflector surface, the power density between the antenna and
the ground can be determined from the following equation:

   Power Density between Reflector and Ground             Sg = P / Asurface                   (8)
                                                             = 6.366 W/m2
                                                             = 0.637 mW/cm2


                                                                                 Exhibit
Radiation Hazard Report                                                          Page 14 of 25

21.    Summary of Calculations

           Table 4. Summary of Expected Radiation levels for Uncontrolled Environment
                                            Calculated Maximum
                                       Radiation Power Density Level
Region                                              (mW/cm2)               Hazard Assessment
1. Far Field (Rff = 28.5 m)                     Sff        0.741            Satisfies FCC MPE
2. Near Field (Rnf = 11.9 m)                    Snf        1.731             Potential Hazard
3. Transition Region (Rnf < Rt < Rff)           St         1.731              Potential Hazard
4. Between Main Reflector and                   Ssr       70.540             Potential Hazard
    Subreflector
5. Main Reflector                               Ssurface   2.546              Potential Hazard
6. Between Main Reflector and Ground            Sg         0.637            Satisfies FCC MPE

            Table 5. Summary of Expected Radiation levels for Controlled Environment
                                           Calculated Maximum
                                          Radiation Power Density
Region                                        Level (mW/cm2)               Hazard Assessment
1. Far Field (Rff = 28.5 m)                    Sff         0.741            Satisfies FCC MPE
2. Near Field (Rnf = 11.9 m)                   Snf         1.731            Satisfies FCC MPE
3. Transition Region (Rnf < Rt < Rff)          St          1.731            Satisfies FCC MPE
4. Between Main Reflector and                  Ssr       70.540              Potential Hazard
    Subreflector
5. Main Reflector                              Ssurface    2.546            Satisfies FCC MPE
6. Between Main Reflector and Ground           Sg          0.637            Satisfies FCC MPE

It is the applicant's responsibility to ensure that the public and operational personnel are not
exposed to harmful levels of radiation.



22.    Conclusions

Based on the above analysis it is concluded that the FCC MPE guidelines have been exceeded (or
met) in the regions of Table 4 and 5. The applicant proposes to comply with the MPE limits by one
or more of the following methods.

The earth station will be located in an area with secured access. All individuals having access to
the antenna will be aware of the Radiation Hazard from the antenna, thus creating a controlled
environment. Warning signs will be in the area to warn individuals of the potential for radiation
hazard.

Finally, occupational exposure will be limited, and the transmitter will be turned off during periods
of maintenance, so that the MPE standard of 5.0 mw/cm**2 will be complied with for those regions
in close proximity to the main reflector, and subreflector, which could be occupied by operating
personnel.


                                                                                        Exhibit
Radiation Hazard Report                                                                 Page 15 of 25




                         bide by the conditions specified in Condition 5208 provided below:
The applicant agrees to abide

        Condition 5208 - The licensee shall take all necessary measures to ensure that the
        antenna does not create potential exposure of humans to radiofrequency radiation
        in excess of the FCC exposure
                                 osure limits defined in 47 CFR 1.1307(b) and 1.1310
        wherever such exposures might occur. Measures must be taken to ensure
        compliance with limits for both occupational/controlled exposure and for general
        population/uncontrolled exposure, as defined in these rule sections. Compliance
        can be accomplished in most cases by appropriate restrictions such as fencing.
        Requirements for restrictions can be determined by predictions based on
        calculations, modeling or by field measurements. The FCC's OET Bulletin 65
        (available on-line
                       line at www.fcc.gov/oet/rfsafety) provides information on predicting
        exposure levels and on methods for ensuring compliance, including the use of
        warning and alerting signs and protective equipment for worker.




I HEREBY CERTIFY THAT I AM THE TECHNICALLY QUALIFIED PERSON RESPONSIBLE FOR THE
PREPARATION OF THE RADIATION HAZARD REPORT, AND THAT IT IS COMPLETE AND CORRECT
TO THE BEST OF MY KNOWLEDGE AND BELIEF.




BY: _

Gary K. Edwards
Senior Manager
COMSEARCH
19700 Janelia Farm Boulevard
Ashburn, VA 20147


DATED: March 28, 2014


                                                                                  Exhibit
Radiation Hazard Report                                                           Page 16 of 25

Analysis of Non-Ionizing Radiation for a Seatel (6009) 1.5-Meter
                     Earth Station System
This report analyzes the non-ionizing radiation levels for a 1.5-meter earth station system. The
analysis and calculations performed in this report comply with the methods described in the FCC
Office of Engineering and Technology Bulletin, No. 65 first published in 1985 and revised in 1997
in Edition 97-01. The radiation safety limits used in the analysis are in conformance with the FCC
R&O 96-326. Bulletin No. 65 and the FCC R&O specifies that there are two separate tiers of
exposure limits that are dependant on the situation in which the exposure takes place and/or the
status of the individuals who are subject to the exposure. The Maximum Permissible Exposure
(MPE) limits for persons in a General Population/Uncontrolled environment are shown in Table 1.
The General Population/Uncontrolled MPE is a function of transmit frequency and is for an
exposure period of thirty minutes or less. The MPE limits for persons in an
Occupational/Controlled environment are shown in Table 2. The Occupational MPE is a function of
transmit frequency and is for an exposure period of six minutes or less. The purpose of the
analysis described in this report is to determine the power flux density levels of the earth station in
the far-field, near-field, transition region, between the subreflector or feed and main reflector
surface, at the main reflector surface, and between the antenna edge and the ground and to
compare these levels to the specified MPEs.

               Table 1. Limits for General Population/Uncontrolled Exposure (MPE)
                  Frequency Range (MHz)          Power Density (mW/cm2)
                          30-300                              0.2
                         300-1500                  Frequency (MHz)*(0.8/1200)
                       1500-100,000                           1.0

                    Table 2. Limits for Occupational/Controlled Exposure (MPE)
                  Frequency Range (MHz)          Power Density (mW/cm2)
                          30-300                              1.0
                         300-1500                  Frequency (MHz)*(4.0/1200)
                       1500-100,000                           5.0

          Table 3. Formulas and Parameters Used for Determining Power Flux Densities
     Parameter                    Symbol           Formula                 Value            Units
     Antenna Diameter                D               Input                   1.5            m
     Antenna Surface Area          Asurface         π D2 / 4                1.77            m2
     Subreflector Diameter          Dsr              Input                  19.0            cm
     Area of Subreflector           Asr             π Dsr 2/4              283.53           cm2
     Frequency                       F               Input                 14250            MHz
     Wavelength                      λ              300 / F              0.021053           m
     Transmit Power                  P               Input                  5.00            W
     Antenna Gain (dBi)             Ges              Input                  43.5            dBi
     Antenna Gain (factor)           G              10Ges/10              22387.2           n/a
     Pi                              π             Constant              3.1415927          n/a
     Antenna Efficiency              η             Gλ2/(π2D2)               0.45            n/a


                                                                                  Exhibit
Radiation Hazard Report                                                           Page 17 of 25



23.    Far Field Distance Calculation

The distance to the beginning of the far field can be determined from the following equation:

   Distance to the Far Field Region                         Rff = 0.60 D2 / λ                     (1)
                                                                = 64.1 m

The maximum main beam power density in the far field can be determined from the following
equation:

   On-Axis Power Density in the Far Field                   Sff = G P / (4 π Rff 2)               (2)
                                                                = 2.166 W/m2
                                                                = 0.217 mW/cm2

24.    Near Field Calculation

Power flux density is considered to be at a maximum value throughout the entire length of the
defined Near Field region. The region is contained within a cylindrical volume having the same
diameter as the antenna. Past the boundary of the Near Field region, the power density from the
antenna decreases linearly with respect to increasing distance.

The distance to the end of the Near Field can be determined from the following equation:

   Extent of the Near Field                                 Rnf = D2 / (4 λ)                      (3)
                                                                = 26.7 m

The maximum power density in the Near Field can be determined from the following equation:

   Near Field Power Density                                 Snf = 16.0 η P / (π D2)               (4)
                                                                = 5.057 W/m2
                                                                = 0.506 mW/cm2

25.    Transition Region Calculation

The Transition region is located between the Near and Far Field regions. The power density
begins to decrease linearly with increasing distance in the Transition region. While the power
density decreases inversely with distance in the Transition region, the power density decreases
inversely with the square of the distance in the Far Field region. The maximum power density in
the Transition region will not exceed that calculated for the Near Field region. The power density
calculated in Section 1 is the highest power density the antenna can produce in any of the regions
away from the antenna. The power density at a distance Rt can be determined from the following
equation:

   Transition Region Power Density                          St = Snf Rnf / Rt                     (5)
                                                               = 0.506 mW/cm2


                                                                              Exhibit
Radiation Hazard Report                                                       Page 18 of 25

Region between the Main Reflector and the Subreflector

Transmissions from the feed assembly are directed     toward the subreflector surface, and are
reflected back toward the main reflector. The most    common feed assemblies are waveguide
flanges, horns or subreflectors. The energy between   the subreflector and the reflector surfaces
can be calculated by determining the power density    at the subreflector surface. This can be
determined from the following equation:

   Power Density at the Subreflector                      Ssr = 4000 P / Asr                  (6)
                                                              = 70.540 mW/cm2

26.    Main Reflector Region

The power density in the main reflector is determined in the same manner as the power density at
the subreflector. The area is now the area of the main reflector aperture and can be determined
from the following equation:

   Power Density at the Main Reflector Surface        Ssurface = 4 P / Asurface               (7)
                                                               = 11.318 W/m2
                                                               = 1.132 mW/cm2


27.    Region between the Main Reflector and the Ground

Assuming uniform illumination of the reflector surface, the power density between the antenna and
the ground can be determined from the following equation:

   Power Density between Reflector and Ground             Sg = P / Asurface                   (8)
                                                             = 2.829 W/m2
                                                             = 0.283 mW/cm2


                                                                                 Exhibit
Radiation Hazard Report                                                          Page 19 of 25

28.    Summary of Calculations

           Table 4. Summary of Expected Radiation levels for Uncontrolled Environment
                                            Calculated Maximum
                                       Radiation Power Density Level
Region                                              (mW/cm2)               Hazard Assessment
1. Far Field (Rff = 64.1 m)                     Sff        0.217            Satisfies FCC MPE
2. Near Field (Rnf = 26.7 m)                    Snf        0.506            Satisfies FCC MPE
3. Transition Region (Rnf < Rt < Rff)           St         0.506            Satisfies FCC MPE
4. Between Main Reflector and                   Ssr       70.540             Potential Hazard
    Subreflector
5. Main Reflector                               Ssurface   1.132              Potential Hazard
6. Between Main Reflector and Ground            Sg         0.283            Satisfies FCC MPE

            Table 5. Summary of Expected Radiation levels for Controlled Environment
                                           Calculated Maximum
                                          Radiation Power Density
Region                                        Level (mW/cm2)               Hazard Assessment
1. Far Field (Rff = 64.1 m)                    Sff         0.217            Satisfies FCC MPE
2. Near Field (Rnf = 26.7 m)                   Snf         0.506            Satisfies FCC MPE
3. Transition Region (Rnf < Rt < Rff)          St          0.506            Satisfies FCC MPE
4. Between Main Reflector and                  Ssr       70.540              Potential Hazard
    Subreflector
5. Main Reflector                              Ssurface    1.132            Satisfies FCC MPE
6. Between Main Reflector and Ground           Sg          0.283            Satisfies FCC MPE

It is the applicant's responsibility to ensure that the public and operational personnel are not
exposed to harmful levels of radiation.



29.    Conclusions

Based on the above analysis it is concluded that the FCC MPE guidelines have been exceeded (or
met) in the regions of Table 4 and 5. The applicant proposes to comply with the MPE limits by one
or more of the following methods.

The earth station will be located in an area with secured access. All individuals having access to
the antenna will be aware of the Radiation Hazard from the antenna, thus creating a controlled
environment. Warning signs will be in the area to warn individuals of the potential for radiation
hazard.

Finally, occupational exposure will be limited, and the transmitter will be turned off during periods
of maintenance, so that the MPE standard of 5.0 mw/cm**2 will be complied with for those regions
in close proximity to the main reflector, and subreflector, which could be occupied by operating
personnel.


                                                                                        Exhibit
Radiation Hazard Report                                                                 Page 20 of 25




                         bide by the conditions specified in Condition 5208 provided below:
The applicant agrees to abide

        Condition 5208 - The licensee shall take all necessary measures to ensure that the
        antenna does not create potential exposure of humans to radiofrequency radiation
        in excess of the FCC exposure
                                 osure limits defined in 47 CFR 1.1307(b) and 1.1310
        wherever such exposures might occur. Measures must be taken to ensure
        compliance with limits for both occupational/controlled exposure and for general
        population/uncontrolled exposure, as defined in these rule sections. Compliance
        can be accomplished in most cases by appropriate restrictions such as fencing.
        Requirements for restrictions can be determined by predictions based on
        calculations, modeling or by field measurements. The FCC's OET Bulletin 65
        (available on-line
                       line at www.fcc.gov/oet/rfsafety) provides information on predicting
        exposure levels and on methods for ensuring compliance, including the use of
        warning and alerting signs and protective equipment for worker.




I HEREBY CERTIFY THAT I AM THE TECHNICALLY QUALIFIED PERSON RESPONSIBLE FOR THE
PREPARATION OF THE RADIATION HAZARD REPORT, AND THAT IT IS COMPLETE AND CORRECT
TO THE BEST OF MY KNOWLEDGE AND BELIEF.




BY: _

Gary K. Edwards
Senior Manager
COMSEARCH
19700 Janelia Farm Boulevard
Ashburn, VA 20147


DATED: March 28, 2014


                                                                                  Exhibit
Radiation Hazard Report                                                           Page 21 of 25

Analysis of Non-Ionizing Radiation for a AVL - 0.96-Meter Earth
                       Station System
This report analyzes the non-ionizing radiation levels for a 0.96-meter earth station system. The
analysis and calculations performed in this report comply with the methods described in the FCC
Office of Engineering and Technology Bulletin, No. 65 first published in 1985 and revised in 1997
in Edition 97-01. The radiation safety limits used in the analysis are in conformance with the FCC
R&O 96-326. Bulletin No. 65 and the FCC R&O specifies that there are two separate tiers of
exposure limits that are dependant on the situation in which the exposure takes place and/or the
status of the individuals who are subject to the exposure. The Maximum Permissible Exposure
(MPE) limits for persons in a General Population/Uncontrolled environment are shown in Table 1.
The General Population/Uncontrolled MPE is a function of transmit frequency and is for an
exposure period of thirty minutes or less. The MPE limits for persons in an
Occupational/Controlled environment are shown in Table 2. The Occupational MPE is a function of
transmit frequency and is for an exposure period of six minutes or less. The purpose of the
analysis described in this report is to determine the power flux density levels of the earth station in
the far-field, near-field, transition region, between the subreflector or feed and main reflector
surface, at the main reflector surface, and between the antenna edge and the ground and to
compare these levels to the specified MPEs.

               Table 1. Limits for General Population/Uncontrolled Exposure (MPE)
                  Frequency Range (MHz)          Power Density (mW/cm2)
                          30-300                              0.2
                         300-1500                  Frequency (MHz)*(0.8/1200)
                       1500-100,000                           1.0

                    Table 2. Limits for Occupational/Controlled Exposure (MPE)
                  Frequency Range (MHz)          Power Density (mW/cm2)
                          30-300                              1.0
                         300-1500                  Frequency (MHz)*(4.0/1200)
                       1500-100,000                           5.0

          Table 3. Formulas and Parameters Used for Determining Power Flux Densities
     Parameter                    Symbol           Formula                 Value            Units
     Antenna Diameter                D               Input                  0.96            m
     Antenna Surface Area          Asurface         π D2 / 4                0.72            m2
     Subreflector Diameter          Dsr              Input                  19.0            cm
     Area of Subreflector           Asr             π Dsr 2/4              283.53           cm2
     Frequency                       F               Input                 14250            MHz
     Wavelength                      λ              300 / F              0.021053           m
     Transmit Power                  P               Input                  5.00            W
     Antenna Gain (dBi)             Ges              Input                  41.2            dBi
     Antenna Gain (factor)           G              10Ges/10              13182.6           n/a
     Pi                              π             Constant              3.1415927          n/a
     Antenna Efficiency              η             Gλ2/(π2D2)               0.64            n/a


                                                                                  Exhibit
Radiation Hazard Report                                                           Page 22 of 25



30.    Far Field Distance Calculation

The distance to the beginning of the far field can be determined from the following equation:

   Distance to the Far Field Region                         Rff = 0.60 D2 / λ                     (1)
                                                                = 26.3 m

The maximum main beam power density in the far field can be determined from the following
equation:

   On-Axis Power Density in the Far Field                   Sff = G P / (4 π Rff 2)               (2)
                                                                = 7.603 W/m2
                                                                = 0.760 mW/cm2

31.    Near Field Calculation

Power flux density is considered to be at a maximum value throughout the entire length of the
defined Near Field region. The region is contained within a cylindrical volume having the same
diameter as the antenna. Past the boundary of the Near Field region, the power density from the
antenna decreases linearly with respect to increasing distance.

The distance to the end of the Near Field can be determined from the following equation:

   Extent of the Near Field                                 Rnf = D2 / (4 λ)                      (3)
                                                                = 10.9 m

The maximum power density in the Near Field can be determined from the following equation:

   Near Field Power Density                                 Snf = 16.0 η P / (π D2)               (4)
                                                                = 17.749 W/m2
                                                                = 1.775 mW/cm2

32.    Transition Region Calculation

The Transition region is located between the Near and Far Field regions. The power density
begins to decrease linearly with increasing distance in the Transition region. While the power
density decreases inversely with distance in the Transition region, the power density decreases
inversely with the square of the distance in the Far Field region. The maximum power density in
the Transition region will not exceed that calculated for the Near Field region. The power density
calculated in Section 1 is the highest power density the antenna can produce in any of the regions
away from the antenna. The power density at a distance Rt can be determined from the following
equation:

   Transition Region Power Density                          St = Snf Rnf / Rt                     (5)
                                                               = 1.775 mW/cm2


                                                                              Exhibit
Radiation Hazard Report                                                       Page 23 of 25

Region between the Main Reflector and the Subreflector

Transmissions from the feed assembly are directed     toward the subreflector surface, and are
reflected back toward the main reflector. The most    common feed assemblies are waveguide
flanges, horns or subreflectors. The energy between   the subreflector and the reflector surfaces
can be calculated by determining the power density    at the subreflector surface. This can be
determined from the following equation:

   Power Density at the Subreflector                      Ssr = 4000 P / Asr                  (6)
                                                              = 70.540 mW/cm2

33.    Main Reflector Region

The power density in the main reflector is determined in the same manner as the power density at
the subreflector. The area is now the area of the main reflector aperture and can be determined
from the following equation:

   Power Density at the Main Reflector Surface        Ssurface = 4 P / Asurface               (7)
                                                               = 27.631 W/m2
                                                               = 2.763 mW/cm2


34.    Region between the Main Reflector and the Ground

Assuming uniform illumination of the reflector surface, the power density between the antenna and
the ground can be determined from the following equation:

   Power Density between Reflector and Ground             Sg = P / Asurface                   (8)
                                                             = 6.908 W/m2
                                                             = 0.691 mW/cm2


                                                                                 Exhibit
Radiation Hazard Report                                                          Page 24 of 25

35.    Summary of Calculations

           Table 4. Summary of Expected Radiation levels for Uncontrolled Environment
                                            Calculated Maximum
                                       Radiation Power Density Level
Region                                              (mW/cm2)               Hazard Assessment
1. Far Field (Rff = 26.3 m)                     Sff        0.760            Satisfies FCC MPE
2. Near Field (Rnf = 10.9 m)                    Snf        1.775             Potential Hazard
3. Transition Region (Rnf < Rt < Rff)           St         1.775              Potential Hazard
4. Between Main Reflector and                   Ssr       70.540             Potential Hazard
    Subreflector
5. Main Reflector                               Ssurface   2.763              Potential Hazard
6. Between Main Reflector and Ground            Sg         0.691            Satisfies FCC MPE

            Table 5. Summary of Expected Radiation levels for Controlled Environment
                                           Calculated Maximum
                                          Radiation Power Density
Region                                        Level (mW/cm2)               Hazard Assessment
1. Far Field (Rff = 26.3 m)                    Sff         0.760            Satisfies FCC MPE
2. Near Field (Rnf = 10.9 m)                   Snf         1.775            Satisfies FCC MPE
3. Transition Region (Rnf < Rt < Rff)          St          1.775            Satisfies FCC MPE
4. Between Main Reflector and                  Ssr       70.540              Potential Hazard
    Subreflector
5. Main Reflector                              Ssurface    2.763            Satisfies FCC MPE
6. Between Main Reflector and Ground           Sg          0.691            Satisfies FCC MPE

It is the applicant's responsibility to ensure that the public and operational personnel are not
exposed to harmful levels of radiation.



36.    Conclusions

Based on the above analysis it is concluded that the FCC MPE guidelines have been exceeded (or
met) in the regions of Table 4 and 5. The applicant proposes to comply with the MPE limits by one
or more of the following methods.

The earth station will be located in an area with secured access. All individuals having access to
the antenna will be aware of the Radiation Hazard from the antenna, thus creating a controlled
environment. Warning signs will be in the area to warn individuals of the potential for radiation
hazard.

Finally, occupational exposure will be limited, and the transmitter will be turned off during periods
of maintenance, so that the MPE standard of 5.0 mw/cm**2 will be complied with for those regions
in close proximity to the main reflector, and subreflector, which could be occupied by operating
personnel.


                                                                                        Exhibit
Radiation Hazard Report                                                                 Page 25 of 25




                         bide by the conditions specified in Condition 5208 provided below:
The applicant agrees to abide

        Condition 5208 - The licensee shall take all necessary measures to ensure that the
        antenna does not create potential exposure of humans to radiofrequency radiation
        in excess of the FCC exposure
                                 osure limits defined in 47 CFR 1.1307(b) and 1.1310
        wherever such exposures might occur. Measures must be taken to ensure
        compliance with limits for both occupational/controlled exposure and for general
        population/uncontrolled exposure, as defined in these rule sections. Compliance
        can be accomplished in most cases by appropriate restrictions such as fencing.
        Requirements for restrictions can be determined by predictions based on
        calculations, modeling or by field measurements. The FCC's OET Bulletin 65
        (available on-line
                       line at www.fcc.gov/oet/rfsafety) provides information on predicting
        exposure levels and on methods for ensuring compliance, including the use of
        warning and alerting signs and protective equipment for worker.




I HEREBY CERTIFY THAT I AM THE TECHNICALLY QUALIFIED PERSON RESPONSIBLE FOR THE
PREPARATION OF THE RADIATION HAZARD REPORT, AND THAT IT IS COMPLETE AND CORRECT
TO THE BEST OF MY KNOWLEDGE AND BELIEF.




BY: _

Gary K. Edwards
Senior Manager
COMSEARCH
19700 Janelia Farm Boulevard
Ashburn, VA 20147


DATED: March 28, 2014



Document Created: 2014-03-28 11:24:07
Document Modified: 2014-03-28 11:24:07

© 2025 FCC.report
This site is not affiliated with or endorsed by the FCC