User Manual

FCC ID: JPZ0034

Users Manual

Download: PDF
FCCID_1025149

StanzaTM                                  SZ-CI-PRG                                              Wireless Control Interfaces
                                                                                                                                 sz-ci-prg- 06.06.08


SZ-CI-PRG Programming Control Interface

                                      Description
                                      The Stanza system is an easy-to-install and easy-to-use lighting
                                      control system designed especially for hotel guest rooms and
                                      similar applications. The system consists of wallbox dimmers,
                                      wallbox switches, line-voltage wallbox keypads, low-voltage
                                      interfaces, and lamp socket dimmer/switches. All of these
                                      devices communicate via radio frequency (RF) within each
                                      individual guest room.
                                      The Stanza programming control interface allows setup,
                                      commissioning, and modification of Stanza systems, and can
                                      also be used to integrate with a PC or other digital equipment
                                      that supports TCP/IP over 10/100 BaseT Ethernet or RS232
                                      connections.
                                       Features
                                     •	Integrates a Stanza guest room lighting control system with a
                                       PC or other digital equipment that supports RS232 or Ethernet
                                       TCP/IP communication.
                                     • Provides a basic serial string command set that allows a PC to
                                       monitor and control lighting.
                                     •	Enables use of a PC to set up and commission Stanza systems.
                                     •	At least one SZ-CI-PRG is required per job for commissioning
                                       or system modification. Programmed and commissioned
                                       systems do not require a SZ-CI-PRG to be present for
                                       continued operation.
                                     • Wireless connection allows easy mounting near integration
                                       device.

                                       FCC Information
                                       Note: This equipment has been tested and found to comply with the limits for
                                       a Class B digital device, pursuant to Part 15 of the FCC rules. These limits are
                                       designed to provide reasonable protection against harmful interference in a residential
                                       installation. This equipment generates, uses and can radiate radio frequency
                                       energy and, if not installed and used in accordance with the instructions,
                                       may cause harmful interference to radio or television reception. However,
                                       there is no guarantee that interference will not occur in a particular installation.
                                       If this equipment does cause harmful interference to radio or television reception,
                                       which can be determined by turning the equipment off and on, the user is
                                       encouraged to try to correct the interference by one or more of the following
                                       measures:
                                       • Reorient or relocate the receiving antenna.
                                       • Increase the seperation between the equipment and receiver.
                                       • Connect the equipment into an outlet on a circuit different from that to
                                       which the receiver is connected.
                                       • Consult the dealer or an experienced radio/TV technician for help.
                                       Caution: Changes or modifications not expressly approved by Lutron
                                       Electronics Co. could void the user’s authority to operate this equipment.
                                       Operation is subject to the following: (1) This device may not cause harmful
                                       interference, and (2) this device must accept any interference received,
                                       including interference that may cause undesired operation.




           R   Specification Submit t a l                                                                                            Page 1
Job Name:                    Model Numbers:

Job Number:


 StanzaTM                                           SZ-CI-PRG                      Wireless Control Interfaces
                                                                                                      sz-ci-prg- 06.06.08


 Specifications
  Standards:                                                 Environment:
•	FCC approved. Complies with the limits for a Class       •	Ambient operating temperature: 32 - 104 °F
  B digital device, pursuant to Part 15 of the FCC           (0 - 40 °C)
  rules                                                    •	Maximum 90% non-condensing relative humidity
  Power:                                                   •	Indoor use only
•	Low-voltage PELV (Class 2: USA).                         •	Cannot be mounted in a metal enclosure (interferes
•	Operating Voltage: 15 - 24 V , 500 mA maximum.             with RF reception).
•	AC adapter included (requires 120 V outlet).               Warranty:
  Integration:                                             • 1-year limited warranty
• Provides one 10/100 Base T (autosensing) Auto-           • 2-year full parts and labor warranty, with 8-year pro-
  MDIX jack for connecting to an Ethernet network            rated parts replacement on commissioned systems
  using TCP/IP.                                              Color/Finish Codes:
• Provides one DB9 RS232 jack for connecting to a          •	Black only
  serial device.
•	Baud rates supported over RS232: 9600, 38400,
  115200.
  Key Design Features:
•	LED status indicators provide device diagnostics
• Power failure memory: if power is interrupted, when
  the power is restored, device will retain all settings
  that were in place prior to the interruption
  System Communication and Capacity:
• Programming control interface communicates with
  other Stanza system components through radio
  frequency (RF) at 434 MHz
•	Multiple RF channels and thousands of system
  addresses prevent interference between systems
• When used only for commissioning and
  programming, programming control interface does
  not count toward the single-system maximum of 31
  Stanza devices




              R   Specification Submit t a l                                                              Page 2
  Job Name:                          Model Numbers:

  Job Number:


         StanzaTM                                                   SZ-CI-PRG                                  Wireless Control Interfaces
                                                                                                                                   sz-ci-prg- 06.06.08


         Dimensions
         Dimensions are in inches (mm)                      2.50
                                                           (63.5)             Mounting holes
                                                                                                                       LEDs and
                                                                                                                      addressing
                                                                                                                    switches on this
                                                                                                                          side
                     Terminal
                  blocks on this                                                                            6.0
                       side                                                                               (152.4)

                                    3.75                                                               4.26
                                   (95.3)                                                            (108.2)




                                                                      5.26
                                                                    (133.6)


                                             1.06
                                            (26.9)




         Mounting

       1. Mount the control interface directly on a surface, as                 Mounting Diagram
          shown in the Mounting Diagram, using screws (not
          included). When mounting, provide sufficient space
          for the antenna and connecting cables. The unit can
          be mounted in any orientation.
          The unit cannot be mounted in a full metal
          enclosure. The antenna is not removable or remotely
          mountable.
          Mount in an accessible location for convenient
          access to addressing switches, LEDs, and terminal
          blocks.                                                                                    Surface
       2. Connect wiring as shown in the Wiring Diagram
                 2.50
          (next page).
                                                                                 Control Interface



3.75                                    4.26




                            5.26




         1.06           R     Specification Submit t a l                                                                               Page 3
         Job Name:                                   Model Numbers:

         Job Number:


  StanzaTM                                                                  SZ-CI-PRG                        Wireless Control Interfaces
                                                                                                                                   sz-ci-prg- 06.06.08


 Wiring Diagram
                               CAT5 Cable:            To PC or AV equipment. For Ethernet link, use CAT5 cable provided to connect to
                              maximum 328 ft.         auxiliary equipment. The Ethernet link LED will light continuously when link is present
                                 (100 m)              and will flash when there is link activity. Additional Ethernet network equipment and
                                                      cables provided by others.



                                               RS232 Cable:            To PC or AV equipment: Use the 9-pin cable
                                              maximum 50 ft.           provided, or follow the chart below.
                                                  (15 m)
                                              COM                                    RS232 Pin Connect Wiring
                                                                      		                 Typical PC or        Pin on
                                               TxD                    RS232 Interface    A/V equipment     9-pin cable
                                                                       Common                Com		               5
                                                                       Receive               TxD		               3
                                              RxD
                                                                       Transmit              RxD		               2
  Ethernet speed
On = 100 Mbit/sec                                                                                                          Diagnostic
 Off = 10 Mbit/sec                                                                                                         LEDs

  Ethernet                                                                                                                  1 2 3 4 567
      link/
   activity
                                                                                                                          LED   1: Power
                            RJ45 jack:                                                                                    LED   2: Ethernet link
                           Ethernet link                                                                                  LED   3: Unused
                          (to PC or A/V                                                                                   LED   4: RS232 link TX
                            equipment)                                PELV (Class 2: USA) Power in
                                                                      500 mA 12 - 24 V                                    LED   5: RS232 link RX
                                                                      (powered by 120 V   transformer, included).         LED   6: Unused
                                                                                                                          LED   7: Unused


 System Overview                                                                   System Communication Notes
                                             Dimmer                                • Stanza lighting controls, keypads, and interfaces
                                  Keypad                                             must be located within 20 feet (6 m) of a Stanza
                                                                                     device configured as a repeater. Multiple devices
                                                                                     configured as repeaters may be necessary to
                                                                                     provide adequate coverage.
                                                                                   •	A total of 3 devices maximum can be configured
                                                                                     as repeaters.
                                                                                   • Devices configured as repeaters must be within
                                                                                     20 feet (6 m) of another device configured as a
                                                                                     repeater.
                                                                                   • Stanza lighting controls cannot be controlled
                                                                                     wirelessly and Stanza keypads will not function
                                       20 ft. (6 m)                                  until they are addressed and programmed.
      20 ft. (6 m) max.                                     20 ft. (6 m) max.
                                        maximum
                                                                                   System Limits
  from repeater device                                      from repeater device


                                                                                   • 31 devices maximum
                                                                                   • 20 feet (6 m) from device to repeater devices
                                                                                   • Dimmers, keypads, or contact closure devices
                                                                                     can be repeaters
                     R      Specification Submit t a l                                                                          Page 4
  Job Name:                                           Model Numbers:

  Job Number:



Document Created: 2008-10-06 11:26:00
Document Modified: 2008-10-06 11:26:00

© 2024 FCC.report