Users Manual

FCC ID: GX9CLMTZB

Users Manual

Download: PDF
FCCID_3246892

Clamp Meter (CLMT-1ZBS)
CL-Meter-ZBS is a ZigBee Clamp Meter aim to monitor and report the total amount of electricity uses in your
facility by connecting the clamp onto the power cable.
The Clamp Meter utilizes ZigBee technology for wireless signal transmission. ZigBee is a wireless
communication protocol that is reliable and has low power consumption and high transmission efficiency. Based
on the IEEE802.15.4 standard, ZigBee allows a large amount of devices to be included in a network and
coordinated for data exchange and signal transmission.
The Clamp Meter serves as an end device in the ZigBee network. It can be included in the ZigBee network to
transmit signal upon activation, but cannot permit any other ZigBee device to join the network through the Clamp
Meter.




Parts Identification
1. Red LED
    Flash twice quickly:
    The Clamp Meter has successfully joined a ZigBee network.
    Flashes once:
    When Clamp Meter is reset.
    Flash once every 20 minutes:
    The Clamp Meter has lost its connection to its current ZigBee network.
2. AC Input cable
3. Current Transformer Cable (CT1)
4. Current Transformer Cable (CT2)
5. Function Button
    -Press the button once to report the value of the meter to the ZigBee network.
    -Press and hold the button for 10 seconds then release to reset the Clamp Meter.
6. Reserved
7. Mounting Hole
8. Mounting Hooks
9. Mounting Bracket


Installation
   Wiring
    WARNING
    Wiring of the device should only be performed by a licensed electrician. The circuit box’s main breaker
    should be turned off to perform installation.
    The insertion hole wire specification is AWG18 or Ø 1.02 (mm²).
    The Clamp specification is 60A Ø10mm
    Please make sure the main power in your facility is also off before installing. Follow the steps below:
    1. Connect AC Input cable to a socket near the Electrical Box to power on the Clamp Meter.
    2. Attach both ends of the Current Transformer Cables first as picture shown below. Once you have attached
       the Current Transformer Cable, start spinning the waterproof latch clock-wise until you have tighten and
       secure both ends of the Current Transformer Cable.




    3. Open the clamp as indicated by below picture. The clamp should be applied onto an electic cable The
       arrow direction on the clamp need to point at the correct direction of the electricity current flows (KL). If
       arrow is faced in reverse direction, the reading will display negative value (-) however it will not influence
       the readings.




                                                                                     K                 L

    4. Follow the schematics below as an example; clip the clamps on the electricity cables on the 2 the
       incoming power cable connected to the Main Circuit Breaker.


   Mounting
    The Clamp Meter has a mounting bracket for mounting purposes.
    1. Use the mounting bracket as template to mark the two holes on the wall for installing screws.
    2. Screw the mounting bracket onto the wall according to marked location. Install wall plugs if necessary.
    3. Locate the hooks of the mounting bracket and line up the hooks with the mounting holes on the Clamp
       Meter. Fit the hooks into the mounting holes as picture below. Installation is now complete.




ZigBee Network Setup
   ZigBee Device Guideline
    ZigBee is a wireless communication protocol that is reliable and has low power consumption and high
    transmission efficiency. Based on the IEEE802.15.4 standard, ZigBee allows a large amount of devices to
    be included in a network and coordinated for data exchange and signal transmission.
    Due to the fundamental structure of ZigBee network, ZigBee device will actively seek and join network after
    powering on. Since performing a task in connecting network may consume some power, it is required to
    follow the instructions to avoid draining battery of a ZigBee device
    - Ensure your ZigBee network router or coordinator is powered on before inserting battery into the ZigBee
    device.
    - Ensure the ZigBee network router or coordinator is powered on and within range while a ZigBee device is
    in use.
    - Do not remove a ZigBee device from the ZigBee network router or coordinator without removing the battery
      from a ZigBee device.
   Joining the ZigBee Network
    As a ZigBee device, the Clamp Meter needs to join a ZigBee network to be able to read the meter. Please
    follow the steps bellow to join the Clamp Meter into ZigBee network.
    The Clamp Meter has 2 ZigBee Endpoints representing 2 current transformers. When joining ZigBee
    network, it will be recognized as 2 separate ZigBee devices and will occupy 2 zones in your ZigBee
    network coordinator.
    1. Plug in the AC Input cable into the socket to power on the Clamp Meter.
    2. Press and hold the function button for 10 seconds and release to search for existing ZigBee network.
       Please make sure the permit-to-join feature on the router or coordinator of your ZigBee network is
       enabled.
    3. After joining the ZigBee network, the Clamp Meter will be registered in the network automatically. Please
       check the ZigBee coordinator, security system control panel or CIE (Control and Indicating Equipment) to
       confirm if joining and registration is successful.
    4. Under normal operation, if the Clamp Meter loses connection to its current ZigBee network, the LED
       indicator will flash every 20 minutes to indicate the situation. Please check your ZigBee network condition
       and Clamp Meter signal range to correct the situation.
   Removing Device from ZigBee Network (Factory Reset)
    To remove the device from current ZigBee network, the Clamp Meter must be put to Factory Reset to
    complete device removal. Factory Reset function will clear the Clamp Meter of its stored setting information
    and prompt the device to search for new ZigBee network.
    Before removing device, make sure the Clamp Meter is within current ZigBee network signal range
    1. Delete the Clamp Meter from current control panel / CIE.
    2. Press and hold the function button for 10 seconds, then release the button to reset device.
    3. Upon reset, the Clamp Meter will clear current ZigBee network setting and transmit signal to ZigBee
       coordinator to remove itself from current ZigBee network. It will then actively search for available ZigBee
       network again and join the network automatically.


 Energy Consumption Monitor
        The Clamp Meter will transmit a signal from the clamp itself with its power consumption data every 10
         minutes to the ZigBee network coordinator.
              Reading from clamp on Current Transformer Cable CT-1 is reported to ZigBee Endpoint 0x01.
              Reading from clamp on Current Transformer Cable CT-2 is reported to ZigBee Endpoint 0x02.
        Whenever the Clamp’s energy output changes by +/- 2W, the Clamp Meter will automatically transmit
         a signal with power consumption data to the ZigBee network coordinator for update.
        The Clamp Meter transmits a signal with power data to coordinator whenever accumulated power
         usage of the clamp increases by 0.1kW/hr.
        The Clamp has an accuracy of +/- 5%.
        To clear the clamp of its accumulated power consumption data, follow steps below:
         1.    Un-plug AC cable to power down Clamp Meter.
         2.    Press and hold the function button, while holding the button, power on the Clamp Meter by
               re-plug in the AC cable.
         3.    Release the function button when red LED starts to quickly flash.
         4.    Un-plug and re-plug AC cable again, clearing is complete.
 Maximum Operation Load
        110V: 6600W and 60A
        230V: 13800W and 60A.
Appendix (For developers only)
                  Scene Selector Cluster ID
Device ID: Consumption Awareness Device :0x000D
Endpoint: 0x01
Server Side                                                                                      Client Side
                                          Mandatory
Basic (0x0000)                                                                               Identify (0x0003)
Identify(0x0003)
Metering (0x0702)
                                                  Optional
None                                                                                                    None

Device ID: Consumption Awareness Device :0x000D
Endpoint: 0x02
Server Side                                                                                      Client Side
                                          Mandatory
Basic (0x0000)                                                                               Identify (0x0003)
Identify(0x0003)
Metering (0x0702)
                                                  Optional
None                                                                                                    None
                    Attribute of Basic Cluster Information
                                                                                                     Mandatory
Identifier           Name               Type             Range        Access         Default
                                                                                                     / Optional
                                    Unsigned 8-bit                     Read
 0x0000           ZCLVersion                           0x00 –0xff                     0x01                M
                                       integer                         only
                                    Unsigned 8-bit                     Read
 0x0001      ApplicationVersion                        0x00 – 0xff                    0x00                O
                                       integer                         only
                                    Unsigned 8-bit                     Read
 0x0003           HWVersion                            0x00 –0xff                       0                 O
                                       integer                         only
                                      Character                        Read          Climax
 0x0004      ManufacturerName                         0 – 32 bytes                                        O
                                        String                         only        Technology
                                      Character                        Read
 0x0005          ModelIdentifier                      0 – 32 bytes              (Model Number)            O
                                        String                         only
                                      Character                        Read         20160620
 0x0006            DateCode                           0 – 16 bytes                                        O
                                       String                          only
 0x0007          PowerSource             8-bit         0x00 –0xff      Read                               M


                                    Enumeration                             only
                                     Character                             Read /
 0x0010      LocationDescription                        0 – 32 bytes                                 O
                                       String                              Write
                                        8-bit                              Read /
 0x0011      PhysicalEnvironment                         0x00 –0xff                    0x00          O
                                    Enumeration                            Write
                                                                           Read /
 0x0012           DeviceEnabled        Boolean           0x00 –0x01                    0x01          M
                                                                           Write
                  Attribute of Identify Cluster Information
                                                                                                 Mandatory
Identifier           Name                Type              Range           Access     Default
                                                                                                 / Optional
                                     Unsigned                              Read /
 0x0000            IdentifyTime                          0x00 –0xffff                 0x0000         M
                                    16-bit integer                         Write
                  Attribute of the Metering Cluster Information
                                                                                                 Mandatory
Identifier           Name                Type              Range           Access     Default
                                                                                                 / Optional
                                     Unsigned                              Read /
 0x0000            IdentifyTime                          0x00 - 0xffff                0x0000         M
                                    16-bit integer                         Write
                    Attribute of the Metering Cluster Information
                                                                                                 Mandatory
Identifier           Name               Type               Range           Access     Default
                                                                                                 / Optional
                                                       0x000000000000
             CurrentSummation        Unsigned                                Read
  0x00                                                        to                       0x00          M
                 Delivered          48-bit integer                           Only
                                                       0xFFFFFFFFFFFF

                    Attributes of the Metering cluster Information
                                                                                                 Mandatory
Identifier              Name                    Type               Range     Access    Default
                                                                                                 / Optional
                                             8-bit             0x00 to        Read
  0x00              UnitofMeasure                                                       0x00         M
                                          Enumeration           0xFF          Only
                                                              0x000000
                                        Unsigned 24-bit                       Read
  0x01                Multiplier                                 to                       1          O
                                           Interger                           Only
                                                              0xFFFFFF
                                                              0x000000
                                        Unsigned 24-bit                       Read
  0x02                 Divisor                                   to                     0xF9         M
                                            Integer                           Only
                                                              0xFFFFFF
                                                               0x00 to        Read
  0x03         SummationFormating         8-bit BitMap                                  0xF9         M
                                                                0xFF          Only
                                                               0x00 to        Read
  0x04            DemandFormating         8-bit BitMap                                  0x94         O
                                                                0xFF          Only
                                                               0x00 to        Read
  0x06         MeteringDeviceType           8-bitMap                                    0x00         M
                                                                0xFF          Only
                    Attributes of the Metering cluster Information
                                                                                                 Mandatory
Identifier            Name               Type               Range          Access     Default
                                                                                                 / Optional
                                     Signed 24-bit       -8,388,607 to      Read
  0x00       InstantaneousDemand                                                       0x00          O
                                        Integer            8,388,607        Only


Federal Communication Commission Interference Statement

This equipment has been tested and found to comply with the limits for a Class B digital
device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a residential installation.
This equipment generates, uses and can radiate radio frequency energy and, if not installed
and used in accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not occur in a
particular installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and on, the
user is encouraged to try to correct the interference by one of the following measures:
. Reorient or relocate the receiving antenna.
. Increase the separation between the equipment and receiver.
. Connect the equipment into an outlet on a circuit different from that to which the receiver
is connected.
. Consult the dealer or an experienced radio/TV technician for help.

FCC Caution: To assure continued compliance, any changes or modifications not expressly
approved by the party responsible for compliance could void the user's authority to operate
this equipment. (Example ‐ use only shielded interface cables when connecting to computer
or peripheral devices).

FCC Radiation Exposure Statement

This equipment complies with FCC RF radiation exposure limits set forth for an uncontrolled
environment. This equipment should be installed and operated with a minimum distance of
20 centimeters between the radiator and your body.

This transmitter must not be co‐located or operating in conjunction with any other antenna
or transmitter.

The antennas used for this transmitter must be installed to provide a separation distance of
at least 20 cm from all persons and must not be co‐located or operating in conjunction with
any other antenna or transmitter.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two
conditions:
(1) This device may not cause harmful interference, and
(2) This device must accept any interference received, including interference that may cause
undesired operation.