manual 3

FCC ID: F8I-DISSMRAA

Users Manual

Download: PDF
FCCID_286791

FCC ID: F8I-DISSMRAA, Partial User Manual, 3 of 4
                                                                                           ADCP-75-136 • Issue 1 • November 2002




                       5. Insert the optical transceiver into the socket until it locks into place.
                       6. Replace the optical transceiver dust cap if it was removed for installation.
                       7. Repeat procedure for each optical transceiver that requires installation.
                       8. Install a port cover (see Figure 18) over each unused optical transceiver socket.

           4.8 Ports 1–6 Optical Connections

                      The optical interface between the DHU and each DEU or DRU is supported by six optical
                      ports. Each of the six optical ports provides a duplex LC-type optical transceiver which is
                      mounted on the DHU front panel. One side of the transceiver provides the optical fiber
                      connection for the forward path (downlink) signal. The other side of the transceiver provides
                      the optical fiber connection for the reverse path (uplink) signal. Use the following procedure to
                      install the forward and reverse path optical fibers and to connect them to the DHU:

                      Danger: This equipment uses a Class 1 Laser according to FDA/CDRH rules. Laser radiation
                      can seriously damage the retina of the eye. Do not look into the ends of any optical fiber. Do
                      not look directly into the optical transceiver of any digital unit or exposure to laser radiation
                      may result. An optical power meter should be used to verify active fibers. A protective cap or
                      hood MUST be immediately placed over any radiating transceiver or optical fiber connector
                      to avoid the potential of dangerous amounts of radiation exposure. This practice also prevents
                      dirt particles from entering the transceiver or connector.

                       1. Obtain the required lengths of single- or multi-mode fiber optic cable.
                       2. Route the fiber optic cable between the DHU and the DEU or DRU (if not already
                          routed) and cut to required length. Allow sufficient slack for dressing and organizing the
                          cables at each unit. Maintain a minimum bend radius of 2 inches (50 mm).

                           Note: The maximum path lengths for the optical fibers are as follows: 500 meters (1,641
                           feet) for 62.5 micron core multi-mode fiber, 750 meters (2,461 feet) for 50 micron core
                           multi-mode fiber, and 10 km (32,808 ft) for 9 micron core single-mode fiber.
                       3. Terminate each optical fiber with a field-installable LC type fiber optic connector as
                          shown in Figure 19. Follow the instructions provided by the connector manufacturer for
                          installing the connector.
                       4. Test each fiber for optical loss as described in Subsection 6.4.2 of this manual.
                       5. Designate one of the fibers as the forward path fiber and the other as the reverse path
                          fiber and label both ends of each fiber with the path designation.
                       6. Use the plastic joiner provided with the LC connectors to join the DHU Port 1 forward
                          and reverse path connectors together (see Figure 19). Make sure the forward path and
                          reverse path connectors are oriented as shown.

                           Note: When viewing any Port 1-6 optical transceiver from the front, the forward path port is
                           on the left and the reverse path port is on the right as shown in Figure 20. In addition, single-
                           mode transceivers are colored blue and multi-mode transceivers are colored black or beige.
                           Both single- and multi-mode transceivers may be mounted on the same DHU.




                                                                                                                       Page 33
                                                                                            © 2002, ADC Telecommunications, Inc.


ADCP-75-136 • Issue 1 • November 2002




                                                OPTICAL CONNECTOR
                                                 ASSEMBLY DETAIL



                    FORWARD PATH (TX)
                       CONNECTOR




                            REVERSE PATH (RX)
                               CONNECTOR

                                                                        PORT 1                         CABLE GUIDE
                                                                        OPTICAL                          DETAIL
                                                                      TRANSCEIVER
                                                          OPTICAL
                                                         CONNECTOR




                                  DESIGNATION CARD AND CLEAR
                                      HOLDER DETAIL    PLASTIC
                                                        COVER


                                                            CARD
                                                                                                    CABLE
                                                                                                    GUIDES

                                                             HOLDER                                             17274-A




                                             Figure 19. Ports 1–6 Fiber Optic Cable Connections



                 TRANSCEIVER COLOR CODE

                 BLUE = SINGLE-MODE (9 MICRON)

                 BLACK/
                 BEIGE = MULTI-MODE (50 OR 62.5 MICRON)




                                                                                                             17150-A




                                                                     DUST CAP (LEAVE IN PLACE
                                                                UNTIL READY TO INSTALL CONNECTOR)
                           FORWARD
                           PATH (TX)
                                        REVERSE
                                        PATH (RX)            DETAIL DRAWING OF
                                                               OPTICAL PORT


                                                    Figure 20. Optical Transceiver Designations



Page 34
© 2002, ADC Telecommunications, Inc.


                                                                                   ADCP-75-136 • Issue 1 • November 2002




           7. Remove the dust caps from the optical fiber connectors and the port 1 optical transceiver.
               Note: Leave the dust cap in place on any unused optical transceiver.
           8. Clean each connector (follow connector supplier’s recommendations) and then insert the
              optical fiber connector pair into DHU optical port 1 (see Figure 19).
           9. Place the optical fibers within the cable guides provided on the cable management tray (see
              Figure 19) and then dress and secure the fibers at the DHU per standard industry practice.
          10. Connect the forward and reverse path optical fibers to the DEU or the DRU as specified
              in the instructions provided with that unit.
          11. Use the designation card provided (see Figure 19) to indicate the location and name of
              the DRU or DEU that is connected to each optical fiber pair. The designation card holder
              may be attached to any convenient flat surface such as the DHU cable management tray
          12. Repeat steps 1–11 for each remaining optical port.

4.9 DC Power Connections

          The DC power interface between the DHU and each DRU is supported by six RJ-45 female
          connectors. Each DHU RJ-45 connector provides nominal 48 Vdc power for the associated
          DRU except when the DRU is powered with an ac/dc converter. A category 3 or 5 twisted pair
          cable is used to feed the power from the DHU to the DRU. Use the following procedure to
          install the DC power cable and to connect it to the DHU.
           1. Obtain the required length of category 3 or 5 twisted pair cable.
           2. Route the cable between the DHU and the DRU (unless already routed) and then cut to
              required length. Allow sufficient slack for dressing and organizing the cable at the DHU.
               Note: The maximum distance for routing power cable is 500 meters (1,641 feet).
           3. Terminate each end of the cable with a male RJ-45 connector. Match the wire color to
              the connector pin as specified in Table 6.
          Caution: The DRU will be damaged if the RJ-45 connector is wired incorrectly.
           4. Perform a continuity test to verify that each wire is properly connected to the terminating
              RJ-45 connector and check the connector for correct polarity (see diagram in Table 6).

                                      Table 6. RJ-45 Connector Pin Designations

                 PIN NUMBER      WIRE COLOR                     CONNECTOR PINS
                       1        White/Green
                       2        Green
                       3        White/Orange
                       4        Orange
                       5        White/Blue       +48 VDC ON PINS 1, 3, 5, AND 7
                                                                                        PIN
                                                 RETURN ON PINS 2, 4, 6, AND 8
                                                                                         8
                       6        Blue                                              PIN
                                                                                   1
                                                                                          16180-A
                       7        White/Brown
                       8        Brown



                                                                                                              Page 35
                                                                                   © 2002, ADC Telecommunications, Inc.


ADCP-75-136 • Issue 1 • November 2002




                  5. Connect the DC power cable to the DHU port 1 DC PWR jack as shown in Figure 21.
                  6. Place the DC power cable within the cable guides provided (see Figure 21) and then
                     dress and secure the cable at the DHU per standard industry practice.




                                RJ-45 CONNECTOR
                                      DETAIL


                                       1
                                           8




                                                                PORT 1                             17275-A
                                                               DC POWER
                                                              CONNECTOR
                                                    RJ-45
                                                  CONNECTOR



                                                                   CABLE GUIDE
                                                                     DETAIL




                                                                                          CABLE
                                                                                          GUIDES




                                               Figure 21. 48 Vdc Power Cable Connection

                  7. Connect the DC power cable to the DRU as specified in the instructions provided with
                     that unit.
                  8. Repeat steps 1–7 for each remaining DRU that will be powered by the DHU.

4.10 External Alarm System Connections

                The alarm interface between the DHU and an external alarm system is supported by a six-
                terminal plug (with screw-type terminals) that connects to a receptacle mounted on the DHU
                front panel. The terminal plug provides connections to normally open (NO) and normally
                closed (NC) dry type alarm contacts for both minor and major alarms. A category 3 or 5 cable
                is typically used to connect the DHU to the external alarm system. Use the following
                procedure to install the alarm wiring and connect it to the DHU:
                  1. Obtain the required length of category 3 or 5 cable.
                  2. Route the cable between the DHU and the external alarm system (if not already routed)
                     and then cut to required length. Allow sufficient slack for dressing and organizing the
                     cable at the DHU.



Page 36
© 2002, ADC Telecommunications, Inc.


                                                                                  ADCP-75-136 • Issue 1 • November 2002




           3. Strip back the outer cable sheath and insulation to expose the wires at both ends of the
              cable and strip back 0.2 inches (5 mm) of insulation each wire.
           4. Connect the Major alarm wire pair to the MAJOR COM/NC or MAJOR COM/NO
              terminals (whichever is required by the external alarm system) on the DHU alarm
              terminal connector (supplied with DHU) as shown in Figure 22.




                                                                ALARM
                                                              CONNECTOR
                                                              RECEPTACLE




                               ALARM
                                                              MINOR
                             CONNECTOR                           NC
                                                          COM
                                                         NO




                                             MINOR
                                             ALARM
                                             WIRES
                                                                             NC
                                                                      NO COM
                                                                        MAJOR


                                                 MAJOR
                                                 ALARM
                                                 WIRES            ALARM CONNECTOR
                                                                       DETAIL
                                                                                            17278-A



                                  Figure 22. External Alarm System Connections


           5. Connect the Minor alarm wire pair to the MINOR COM/NC or MINOR COM/NO
              terminals (whichever is required by the external alarm system) on the DHU alarm
              terminal connector as shown in Figure 22.
           6. Insert the alarm terminal connector into the receptacle on the DHU front panel.
           7. Connect the Major and Minor alarm wire pairs to the appropriate terminals on the
              external alarm system.
           8. Dress and secure cable per standard industry practice.

4.11 AC Power Connections

          The AC power interface between the DHU and the AC power source is supported by a 3-wire
          AC power cord connector located on the DHU front panel. The AC connector provides a
          connection point for the power cord which is provided separately with the DHU. Use the
          following procedure to install the AC power cord:



                                                                                                             Page 37
                                                                                  © 2002, ADC Telecommunications, Inc.


ADCP-75-136 • Issue 1 • November 2002




                  1. Locate the AC power cord which is provided separately with the DHU. Use only the AC
                     power cord provided with the DHU or an equivalent UL/CUL listed 3-conductor, 18
                     AWG cord terminated in a molded-on plug cap rated 125 V, 15 A with a maximum
                     length of 6 feet (1.8 m).

                       Note: The DHU is intended to be used with a 3-wire grounding type plug which has a
                       grounding pin. Equipment grounding is required to ensure safe operation. Do not defeat
                       the grounding means. Verify DHU is reliably grounded when installed.
                  2. Place the DHU AC power ON/OFF switch, shown in Figure 23, in the OFF position
                     (press O).




                                                                                                 17276-A


                                         AC POWER CORD



                                                Figure 23. AC Power Connection

                  3. Connect the receptacle end of the power cord to the AC connector on the DHU.
                  4. Route the plug end of the power cord to the specified AC outlet (per the system design)
                     and connect plug to outlet.
                Warning: The current rating of the DHU is 2.0 Amps at 120 Vac. Avoid overloading circuits
                which may cause damage to over-current protection devices and supply wiring.
                  5. Dress and secure cable per standard industry practice.
                  6. When all units of the Digivance ICS have been installed, refer to Section 4 of this
                     manual for the system power up and test procedures.

4.12 Create As-Built Drawing

                Following installation, create an “as-built” drawing of the complete Digivance ICS system.
                Using a drawing of the building floor plan, show the installed location of each piece of
                equipment including the various Digivance electronic units, the antennas, the interface units,
                and the microcell (if used). In addition, show the location and routing of all copper, coaxial,
                and fiber optic cable runs used with the system. Retain the as-built drawing for reference when
                troubleshooting or when planning for system expansion.



Page 38
© 2002, ADC Telecommunications, Inc.


                                                                             ADCP-75-136 • Issue 1 • November 2002




5   SYSTEM OPERATION

           This section provides guidelines for turning-up the Digivance ICS, verifying that all units are
           operating properly, testing to ensure that all performance requirements are satisfied, and
           correcting any installation problems. This process assumes that the various units that comprise
           the Digivance ICS have been installed in accordance with the system design plan and the BTS
           interface device has been installed and tested.


5.1 Tools and Materials

           The following tools and materials are required in order to complete the procedures in this
           section:
           •     Portable spectrum analyzer
           •     Portable test transmitter
           •     Cell phone
           •     Pencil or pen
           •     Writing pad


5.2 Turn-Up System and Verify Operation

           The process of turning-up the system and verifying operation involves powering up the
           various system components and then verifying that the LED indicators show normal operation.
           Refer to Tables 7, 8, and 9 as needed for a complete description of the unit LED indicators.
           Use the following procedure to power-up the system. If any unit does not respond as
           described, refer to Subsection 5.3 for the correction procedures.
               1. Temporarily disconnect the alarm system or notify alarm system provider that testing is
                  in progress.
               2. Verify that each AC powered unit is connected to the appropriate outlet.
               3. Place the ON/OFF switch on the DHU in the ON position (press I).
               4. Verify that the UNIT LED and the OVERDRIVE LED on the DHU turn yellow (for
                  approximately 6 seconds) and then green.
               5. Place the PORT 1 ON/OFF switch on the DHU in the ON position (press I).
               6. If a DEU is connected to port 1, proceed to step 7. If a DRU is connected to port 1, skip
                  steps 7 and 8 and proceed to step 9.
               7. Place the ON/OFF switch on the DEU in the ON position (press I).
               8. Verify that the UNIT LED on the DEU turns yellow (for approximately 6 seconds) and
                  then green.
               9. Verify that the PORT 1 OK/NOK LED on the DHU turns yellow (for approximately 6
                  seconds) and then green.
           10. If a DEU is connected to PORT 1, proceed to step 11. If a DRU is connected to PORT 1,
               skip steps 11 through 13 and proceed to step 14.



                                                                                                         Page 39
                                                                              © 2002, ADC Telecommunications, Inc.


ADCP-75-136 • Issue 1 • November 2002




                 11. Verify that the HOST PORT LED on the DEU turns green.
                 12. Place the PORT 1 ON/OFF switch on the DEU in the ON position (press I).
                 13. Verify that the PORT 1 OK/NOK LED on the DEU turns yellow (for approximately six
                     seconds) and then green.
                 14. Verify that the STATUS LED on the DRU connected to PORT 1 turns yellow (for
                     approximately six seconds) and then green.
                 15. Repeat the procedure covered in steps 5 through 14 for each of the remaining DHU
                     optical ports (ports 2 through 6) that is connected to a DEU or a DRU.
                 16. Reconnect the alarm system and notify alarm system provider that system is operational.


                                            Table 7. Digital Host Unit LED Indicators

                INDICATOR               COLOR    DESCRIPTION
                UNIT                             Indicates when the DHU is normal or faulty.
                LED                     Green    DHU in normal state, no faults detected.
                                        Yellow   DHU high temperature fault detected. (see Note)
                                         Red     DHU fault detected (see Note).
                                         Off     AC power off to DHU or DHU internal fault.
                PORT 1–6                         Indicates if any connected DEU or DRU is normal or faulty or if the
                OK/NOK                           optical inputs from any connected DEU or DRU are normal or lost.
                LEDs                  Green      All connected units in normal state, no faults detected.
                                     Yellow      High temperature fault detected in connected DEU. (see Note)
                                       Red       Fault detected in a connected DEU or DRU. (see Note)
                                     (steady)
                                       Red       No reverse path optical signal detected from a connected DEU or DRU or
                                    (blinking)   excessive reverse path errors detected from a connected DEU or DRU.
                                                 (see Note)
                                         Off     Port disabled (via front panel switch) or DHU internal fault.
                OVERDRIVE                        Indicates when the forward path RF input is below or above the
                LED                              overdrive threshold.
                                        Green    RF input signal level at DHU below overdrive threshold.
                                         Red     RF input signal level at DHU above overdrive threshold.
                Note: Detection of any fault will generate an alarm. A high temperature fault will generate a minor
                alarm (yellow LED). All other types of faults will generate a major alarm (red LED).




Page 40
© 2002, ADC Telecommunications, Inc.


                                                                       ADCP-75-136 • Issue 1 • November 2002




                             Table 8. Digital Expansion Unit LED Indicators

INDICATOR         COLOR       DESCRIPTION
UNIT                          Indicates when the DEU is normal or faulty.
LED              Green        DEU in normal state, no faults detected.
                 Yellow       DEU high temperature fault detected. (see Note)
                  Red         DEU internal fault detected. (see Note)
                  Off         AC power off to DEU or DEU internal fault.
HOST PORT                     Indicates when the optical inputs from the DHU or supporting
LED                           DEU are normal or lost.
                  Green       DHU or supporting DEU in normal state, no faults detected.
                   Red        No forward path optical signal detected from DHU or supporting DEU
                (blinking)    or excessive forward path errors detected from DHU or supporting
                              DEU. (see Note).
                   Off        DEU internal fault.
PORT 1–6                      Indicates if any connected DEU or DRU is normal or faulty or if the
OK/NOK                        optical inputs from any connected DEU or DRU are normal or lost.
LEDs              Green       DRU or remote DEU in normal state, no faults detected.
                 Yellow       High temperature fault detected in connected DEU. (see Note)
                   Red        Fault detected in a connected DEU or DRU. (see Note)
                 (steady)
                   Red        No reverse path optical signal detected from a connected DEU or DRU
                (blinking)    or excessive reverse path errors detected from a connected DEU or
                              DRU.
                   Off        Port disabled (via front panel switch) or DEU internal fault.
Note: Detection of any fault will generate an alarm. A high temperature fault will generate a minor
alarm (yellow LED). All other types of faults will generate a major alarm (red LED).



                              Table 9. Digital Remote Unit LED Indicator

INDICATOR         COLOR       DESCRIPTION
STATUS                        Indicates if the DRU is normal or faulty or if the forward path optical
LED                           inputs to the DRU are normal or lost.
                  Green       DRU in normal state, no faults detected.
                   Red        DRU internal fault detected. (See Note)
                 (steady)
                   Red        No forward path optical signal from the DHU or DEU detected.
                (blinking)
                    Off       DC power off to DRU or DRU internal fault.
Note: Detection of any fault will generate an alarm. A high temperature fault will generate
a minor alarm (yellow LED). All other types of faults will generate a major alarm (red LED).




                                                                                                   Page 41
                                                                        © 2002, ADC Telecommunications, Inc.


ADCP-75-136 • Issue 1 • November 2002




5.3 Test System Performance

                Testing the performance of the system involves completing various RF tests and telephone
                service tests that verify if the system is functioning properly. Use the following procedure to
                test the system performance:

                  1. Verify that the forward path (downlink) input signal level at the DHU is optimized. The peak
                     COMPOSITE forward path input signal level at the DHU should be set at –20 dBm.
                       Note: In a CDMA system, the power level is dependent on the traffic. For optimum
                       operation in a CDMA system, the input signal level should be set below the level of the
                       pilot signal.
                  2. Verify that the reverse path (uplink) signal level at the local BTS or donor antenna is
                     optimized. Note that the reverse path output signal level required is dependent on service
                     provider signal to noise requirements, ICS system noise floor, the service provider
                     equipment, and the system configuration.
                  3. Check and record the Received Signal Strength Indication (RSSI) and any spurious
                     emission levels at and between all DRU antennas. Analyze all DRU’s and the DHU
                     interface using a spectrum analyzer.
                  4. Plot the RSSI levels on a floor plan of the building and check against the pre-installation
                     RSSI levels to determine the overall and average RSSI improvement attributed to the
                     Digivance ICS. Check the entire Digivance coverage area.
                  5. Verify call processing and voice quality within the coverage areas. Initiate and receive
                     multiple long and short duration calls. Document the performance and address any issues
                     as calls are processed within the entire coverage area. Assuming a properly functioning
                     server RF link and BTS and a properly designed and optimized ICS system, there should
                     be no clicks, mutes, clipping, or crackles within the coverage area. In a wireless office
                     application, hand off will not occur.
                  6. If the DHU interfaces with a local BTS (microcell), verify the handoff function by
                     placing a call and confirming handoffs between the Digivance/microcell coverage area
                     and the outdoor macrocell coverage area (macro system) and vice versa. The handoff
                     should take place without any noticeable call quality or performance issues.
                  7. If the DHU interfaces with a remote BTS through a donor antenna, verify call quality by
                     placing a call and then walking between the Digivance coverage area and an area
                     receiving good coverage directly from the cell site base station. There should be no
                     noticeable difference in call quality.
                  8. Following service provider guidelines, test the 411 and 911 links to verify the routing of
                     emergency and special services calls on local BTS configurations.
                  9. Verify that the alarm reporting system functions properly by turning the DHU off. This
                     should generate a major and minor alarm and operate both the major and minor alarm
                     contacts. Check for alarm confirmation from the service provider’s local switch and
                     Network Operations Center (NOC). Note that this tests only the external alarm system
                     and does not verify operation of the Digivance alarm reporting system.




Page 42
© 2002, ADC Telecommunications, Inc.


                                                                            ADCP-75-136 • Issue 1 • November 2002




6   SYSTEM MAINTENANCE PROCEDURES

           This section explains the alarm reporting system, provides a method for isolating and
           troubleshooting faults, and provides procedures for replacing the modular transceivers and the
           DHU or DEU cooling fans.

           The Digivance ICS requires no regular maintenance to insure continuous and satisfactory
           operation. Maintenance, as it applies to the Digivance ICS, primarily involves diagnosing and
           correcting service problems as they occur. When an alarm is reported, it will be necessary to
           follow a systematic troubleshooting procedure to locate the problem. Once the source of the
           problem is isolated, the appropriate corrective action can be taken to restore service. The only
           unit components that can be replaced are the cooling fans that mount in the DHU and DEU
           and the modular optical transceivers. The failure of any other component within a unit will
           require replacement of that unit.

6.1 Tools and Materials

           The following tools and materials are required in order to complete the procedures in this
           section:
           •   ESD wrist strap
           •   IR filtering safety glasses
           •   Optical loopback device (such as Stratos Lightwave LC5 series) and LC duplex adapter
           •   Optical power meter
           •   Magnification device for inspecting LC connectors
           •   Laser light source
           •   Multimeter
           •   Cell phone
           •   RJ-45 circuit access tool (such as the Harris 8-wire Banjo Adapter)
           •   Medium and small size flat-bladed screwdrivers
           •   TORX screwdriver (T10)

6.2 Fault Detection and Alarm Reporting

           Detection of a fault by the Digivance ICS will generate an external alarm response. LED
           indicators are provided on the front panel of the various units to indicate when a fault is
           detected. In addition to LED indicators, the DHU also provides normally open (NO) and
           normally closed (NC) dry alarm contacts for reporting minor and major alarms to an external
           alarm system. A minor alarm is defined as a high temperature condition. A major alarm is
           defined as any fault condition except high temperature.

           When the DHU alarm contacts are connected to an external alarm system, detection of a fault
           will generate an alarm at the Network Operations Center (NOC). However, various types of
           faults may not generate an alarm response. In this case, the first indication of a problem will
           probably be from cell phone users reporting a loss of service or poor service. Whenever a
           problem is reported, whether by a external alarm system or by a call from a user, refer to
           Subsection 6.3 to isolate and correct the fault.


                                                                                                        Page 43
                                                                             © 2002, ADC Telecommunications, Inc.


ADCP-75-136 • Issue 1 • November 2002




6.3 Fault Isolation and Troubleshooting
                Fault isolation and troubleshooting guidelines are provided in Tables 11, 12, 13, and 14. When an
                alarm is reported, determine the type of alarm generated (minor or major) and then check the LED
                indicators on the DHU and note any that are red, yellow, or off. If any of the Port 1–6 OK/NOK
                LED indicators on the DHU are red or yellow, also check the LED indicators on the connected
                DEU’s and/or DRU’s and note if any are red or yellow. Start the troubleshooting process at the
                DHU and then work toward the unit where the alarm originated. The troubleshooting tables are
                organized according to unit type. Locate the problem in the appropriate table, check out the
                suggested possible causes, and take corrective action as required.

                Figure 24 shows two basic ICS system configurations. The troubleshooting tables list possible
                causes for various problems. If the cause of a particular problem is specific to either of the two
                system configurations shown in Figure 24, the type of system configuration (1 or 2) will be
                referenced in the table.
                                                    DIGITAL HOST UNIT                         DRU
                                                                                   REV

                                        (1)
                                                                                   FWD




                              DIGITAL HOST UNIT                               DIGITAL EXPANSION UNIT               DRU
                                                              REV                                           REV

                (2)
                                                             FWD                                            FWD

                                                                                                                     17962-A



                                                  Figure 24. ICS System Basic Configurations


                                         Table 11. DHU Fault Isolation and Troubleshooting Guidelines
                Alarm Type        LED                       LED COLOR
                Minor             UNIT                      Yellow
                Problem : The DHU is overheating.
                POSSIBLE CAUSE                                           CORRECTIVE ACTION/COMMENTS
                1. Air intake or exhaust openings to DHU                 1. Remove cause of air-flow blockage.
                   chassis blocked.
                2. Ambient temperature > 50º C/122º F.                   2. Reduce ambient temperature.
                3. Faulty fan.                                           3. Replace fan (see Subsection 6.5).
                Alarm Type        LED                       LED COLOR
                Major             UNIT                      Red
                Problem : The DHU detects an internal circuitry fault.
                POSSIBLE CAUSE                                           CORRECTIVE ACTION/COMMENTS
                1. Faulty DHU.                                           1. Replace DHU.

                                                                                                                  (Continued)




Page 44
© 2002, ADC Telecommunications, Inc.


                                                                                ADCP-75-136 • Issue 1 • November 2002




              Table 11. DHU Fault Isolation and Troubleshooting Guidelines (Continued)

Alarm Type       LED                               LED COLOR
Major            OVERDRIVE                         Red
Problem: Forward path RF input level too high.
POSSIBLE CAUSE                                           CORRECTIVE ACTION/COMMENTS
1. Incorrect attenuation in forward path RF              1. Adjust attenuation at interface device.
   coaxial link.
Alarm Type       LED                      LED COLOR
Minor            OK/NOK                   Yellow
Problem: The DHU is receiving a minor alarm signal from the DEU.
POSSIBLE CAUSE                                           CORRECTIVE ACTION/COMMENTS
1. The connected DEU is overheating (2).                 1. Check DEU UNIT indicator and then refer to the
                                                            appropriate troubleshooting section for procedures.
Alarm Type       LED                      LED COLOR
Major            OK/NOK                   Blinking Red
Problem: The DHU is not receiving an optical signal from the DRU or DEU.
POSSIBLE CAUSE                                           CORRECTIVE ACTION/COMMENTS
1. Forward and reverse path optical fibers               1. Check fiber connections for correct polarity and
   reversed between DHU and DRU (1); or                     reverse connectors at either unit if mismatched.
   between DHU and DEU (2).
2. Faulty reverse path optical fiber between DHU         2. Clean optical connector and then test optical fiber.
   and DRU (1).                                             Repair or replace if faulty (see Subsection 6.4.2).
3. Faulty optical receive port at DHU or faulty          3. Make sure transceiver is fully plugged in and then
   optical transmit port at DRU (1).                        test optical port. Replace optical transceiver if
                                                            port is faulty (see Subsection 6.4.1).
4. Faulty forward or reverse path optical fiber          4. Clean optical connectors and then test optical
   between DHU and DEU (2).                                 fibers. Repair or replace if faulty (see Subsection
                                                            6.4.2).
Alarm Type       LED                      LED COLOR
Major            OK/NOK                   Red
Problem: The DHU is receiving a major alarm signal from the DRU.
POSSIBLE CAUSE                                           CORRECTIVE ACTION/COMMENTS
1. Faulty forward path optical fiber between             1. Clean optical connector and then test optical fiber.
   DHU and DRU (1).                                         Repair or replace if faulty (see Subsection 6.4.2).
2. Faulty optical transmit port at DHU or faulty         2. Make sure transceiver is fully plugged in and then
   optical receive port at DRU (1).                         test optical port. Replace optical transceiver if
                                                            port is faulty (see Subsection 6.4.1).
3. The DRU is faulty (1 and 2).                          3. Check DEU UNIT indicator or DRU STATUS
                                                            indicator and then refer to appropriate trouble-
                                                            shooting section for procedures.
4. Faulty forward or reverse path optical fiber          4. Check the status of the OK/NOK LED on the
   between the DEU and DRU (2).                             DEU and then Refer to Table 12.




                                                                                                           Page 45
                                                                                © 2002, ADC Telecommunications, Inc.


ADCP-75-136 • Issue 1 • November 2002




                                        Table 12. DEU Fault Isolation and Troubleshooting Guidelines
                Alarm Type        LED                      LED COLOR
                Minor             UNIT                     Yellow
                Problem : The DEU is overheating.
                POSSIBLE CAUSE                                           CORRECTIVE ACTION/COMMENTS
                1. Air intake or exhaust openings to DEU                 1. Remove cause of air-flow blockage.
                   chassis blocked.
                2. Ambient temperature > 50º C/122º F.                   2. Reduce ambient temperature.
                3. Faulty fan.                                           3. Replace fan (see Subsection 6.5).
                Alarm Type        LED                      LED COLOR
                Major             UNIT                     Red
                Problem : The DEU detects an internal circuitry fault.
                POSSIBLE CAUSE                                           CORRECTIVE ACTION/COMMENTS
                1. Faulty DEU.                                           1. Replace DEU.
                Alarm Type        LED                             LED COLOR
                Major             HOST PORT                       Blinking Red
                Problem: The DEU is not receiving an optical signal from the DHU.
                POSSIBLE CAUSE                                           CORRECTIVE ACTION/COMMENTS
                1. Faulty forward path optical fiber between DEU 1. Clean optical connector and then test optical fiber.
                   and DHU (2).                                     Repair or replace if faulty (see Subsection 6.4.2).
                2. Faulty optical receive port at DEU or faulty  2. Make sure transceiver is fully plugged it and then
                   optical transmit port at DHU (2).                test optical port. Replace optical transceiver if
                                                                    port is faulty (see Subsection 6.4.1).
                Alarm Type        LED                      LED COLOR
                Minor             OK/NOK                   Yellow
                Problem: The DEU is receiving a minor alarm signal from a connected DEU.
                POSSIBLE CAUSE                                           CORRECTIVE ACTION/COMMENTS
                1. The connected DEU is overheating.                     1. Check DEU UNIT indicator and then refer to the
                                                                            appropriate troubleshooting section for procedures.
                Alarm Type        LED                      LED COLOR
                Major             OK/NOK                   Blinking Red
                Problem: The DEU is not receiving an optical signal from the DRU.
                POSSIBLE CAUSE                                           CORRECTIVE ACTION/COMMENTS
                1. Forward and reverse path optical fibers               1. Check fiber connections for correct polarity and
                   reversed between DEU and DRU.                            reverse connectors at either unit if mismatched.
                2. Faulty reverse path optical fiber between DEU         2. Clean optical connector and then test optical fiber.
                   and DRU.                                                 Repair or replace if faulty (see Subsection 6.4.2).
                3. Faulty optical receive port at DEU or faulty          3. Make sure transceiver is fully plugged in and then
                   optical transmit port at DRU.                            test optical port. Replace optical transceiver if
                                                                            port is faulty (see Subsection 6.4.1).

                                                                                                                          (Continued)




Page 46
© 2002, ADC Telecommunications, Inc.


                                                                               ADCP-75-136 • Issue 1 • November 2002




               Table 12. DEU Fault Isolation and Troubleshooting Guidelines (Continued)

Alarm Type       LED                       LED COLOR
Major            OK/NOK                    Red
Problem: The DEU is receiving a major alarm signal from the connected DRU.
POSSIBLE CAUSE                                          CORRECTIVE ACTION/COMMENTS
1. Faulty forward path optical fiber between DEU 1. Clean optical connector and then test optical fiber.
   and DRU.                                         Repair or replace if faulty (see Subsection 6.4.2).
2. Faulty optical transmit port at DEU or faulty 2. Make sure transceiver is fully plugged in and then
   optical receive port at DRU.                     test optical port. Replace optical transceiver if
                                                    port is faulty (see Subsection 6.4.1).
3. The connected DRU is faulty.                  3. Check DRU STATUS indicator and then refer
                                                    to appropriate troubleshooting section for
                                                    procedures.


                       Table 13. DRU Fault Isolation and Troubleshooting Guidelines

Alarm Type       LED                       LED COLOR
Major            STATUS                    Off
Problem : The DRU is not powered.
POSSIBLE CAUSE                                          CORRECTIVE ACTION/COMMENTS
1. DC power cable open.                                 1. Test cable for continuity and repair or replace if
                                                           faulty.
2. No power or insufficient power output from           2. Check DC voltage level at the DRU (see Subsection
   ac/dc power converter, DHU (1), or DEU (2).             6.4.3). Replace converter, DHU, or DEU (whichever
                                                           applies) if voltage is not within 34 to 48 Vdc.
3. Faulty DRU.                                          3. Replace DRU.
Alarm Type       LED                       LED COLOR
Major            STATUS                    Blinking Red
Problem : The DRU is not receiving an optical signal from the DHU or DEU; or the DHU or DEU is not receiving
an optical signal from the DRU.
POSSIBLE CAUSE                                          CORRECTIVE ACTION/COMMENTS
1. Faulty forward or reverse path optical fiber         1. Clean optical connector and then test optical fiber.
   between DHU and DRU (1), DEU and                        Repair or replace if faulty (see Subsection 6.4.2).
   DRU (2), or DEU and DHU (2).
2. Faulty optical transmit or receive port at the       2. Make sure transceiver is fully plugged it and then
   DHU (1) or DEU (2); or faulty optical                   test optical port. Replace optical transceiver if
   transmit or receive port at DRU (1 and 2).              port is faulty (see Subsection 6.4.1).
Alarm Type       LED                       LED COLOR
Major            STATUS                    Red
Problem: The DRU detects an internal circuitry fault.
POSSIBLE CAUSE                                          CORRECTIVE ACTION/COMMENTS
1. Faulty DRU.                                          1. Replace DRU.




                                                                                                          Page 47
                                                                               © 2002, ADC Telecommunications, Inc.


ADCP-75-136 • Issue 1 • November 2002




                                        Table 14. System Fault Isolation and Troubleshooting Guidelines

                Alarm Type        LED                      LED COLOR
                None              All                      Normal
                Problem: Loss of phone service from one DRU. Service normal at all other DRU’s.
                POSSIBLE CAUSE                                       CORRECTIVE ACTION/COMMENTS
                1. DRU antenna cable disconnected.                   1. Re-connect DRU antenna cable to DRU.
                2. DRU antenna obstructed or misdirected.            2. Remove antenna obstruction or re-orient antenna.
                3. DRU antenna faulty.                               3. Replace antenna.
                4. DRU faulty.                                       4. Replace DRU.
                Alarm Type        LED                      LED COLOR
                None              All                      Normal
                Problem: Loss of phone service from all DRU’s.
                POSSIBLE CAUSE                                       CORRECTIVE ACTION/COMMENTS
                1. Faulty coaxial connection between DHU             1. Check forward path signals at the DHU. Check
                   and the interface device.                            reverse path signals at the interface device.
                2. Faulty coaxial connection between interface       2. Check forward path signals at the interface
                   device and the BTS or donor antenna.                 equipment. Check reverse path signals at the BTS or
                                                                        antenna.
                3. Faulty interface equipment.                       3. Adjust or replace interface equipment.
                4. Faulty DHU                                        4. Replace DHU.
                5. Fault with cellular network or equipment.         5. Contact cell service provider and verify that
                                                                        cellular network and equipment is operational.
                Alarm Type        LED                      LED COLOR
                None              All                      Normal
                Problem: Calls may be originated and terminated but service is noisy.
                POSSIBLE CAUSE                                       CORRECTIVE ACTION/COMMENTS
                1. Some electrical device in the immediate           1. Try turning off each device that may be causing
                  vicinity is creating interference.                    interference and see if problem corrects itself.
                Alarm Type        LED                      LED COLOR
                None              All                      Normal
                Problem: Sudden high rate of blocked calls (delay dial tone).
                POSSIBLE CAUSE                                       CORRECTIVE ACTION/COMMENTS
                1. Too many users for the number of channels         1. Wait a few minutes and try dialing again. Upgrade
                  available.                                            service if additional channels are required.
                2. Faulty DHU, DEU, or DRU.                          2. Replace defective unit.




Page 48
© 2002, ADC Telecommunications, Inc.


                                                                               ADCP-75-136 • Issue 1 • November 2002




6.4 Test Procedures

          6.4.1   Optical Loopback Test Procedure

          Dirty optical connectors, a faulty optical transceiver, a break in an optical fiber, or a fault in an
          optical connector will interrupt communications between fiber-linked components. Use the
          following procedure to determine if a fault exists with an optical port or with an optical fiber:
          Danger: This equipment uses a Class 1 Laser according to FDA/CDRH rules. Laser radiation
          can seriously damage the retina of the eye. Do not look into the ends of any optical fiber. Do
          not look directly into the optical transceiver of any digital unit or exposure to laser radiation
          may result. An optical power meter should be used to verify active fibers. A protective cap or
          hood MUST be immediately placed over any radiating transceiver or optical fiber connector
          to avoid the potential of dangerous amounts of radiation exposure. This practice also prevents
          dirt particles from entering the transceiver or connector.

           1. Put on the IR filtering safety glasses.
           2. At the DHU or supporting DEU, place the PORT ON/OFF switch for the fiber port or
              fiber to be tested in the OFF position (press O).
           3. Disconnect the optical connectors for the fiber port to be tested and place a dust cap over
              each connector.
           4. Plug a loopback into the optical port to be tested as shown in Figure 25.

                      OPTICAL LOOPBACK
                      CONNECTION DETAIL




                                                                                                               17277-A




                                                              PORT 1
                                                              OPTICAL
                                                            TRANSCEIVER


                                                OPTICAL
                                               LOOPBACK


                                          Figure 25. DHU/DEU Loopback Test


           5. At the DHU or supporting DEU, place the PORT ON/OFF switch in the ON position
              (press I).




                                                                                                          Page 49
                                                                               © 2002, ADC Telecommunications, Inc.


ADCP-75-136 • Issue 1 • November 2002




                  6. The PORT OK/NOK LED will turn either blinking red or green. If the LED turns
                     blinking red, the optical port is faulty. Replace the optical transceiver and then recheck
                     system operation. If the LED turns green, the optical port is good. Proceed to step 7 to
                     continue the test procedure.
                  7. Place the PORT ON/OFF switch in the OFF position (press O).
                  8. Disconnect the loopback from the DHU or supporting DEU.
                  9. Clean and then reconnect the optical fiber connectors to the DHU or DEU optical port.
                 10. Disconnect the optical connectors at the DRU optical port or remote DEU host port (far
                     end of fiber).
                 11. Clean the optical fiber connectors and then using an LC optical adapter, connect the
                     loopback to the connectors as shown in Figure 26.

                                        NOTE: iF THE DISTANCE BETWEEN THE DHU/DEU AND THE
                                        DRU EXCEEDS THE DISTANCE SHOWN BELOW, THE
                                        REMOTE LOOPBACK TEST WILL NOT WORK.

                                        62.5 MICRON MULTI-MODE FIBER - 250 METERS
                                        50 MICRON MULTI-MODE FIBER - 375 METERS
                                        9 MICRON SINGLE-MODE FIBER - 5 KILOMETERS

                                                                                             OPTICAL
                                                                                            LOOPBACK

                                                                                               16768-B

                                                                            OPTICAL
                                                                            ADAPTER

                                                                 OPTICAL
                                                                CONNECTOR


                                                   Figure 26. Optical Fiber Loopback Test


                 12. Insert a dust plug into the DRU optical port or remote DEU host port.
                 13. At the DHU or supporting DEU, place the PORT ON/OFF switch in the ON position
                     (press I).
                14. The PORT OK/NOK LED will turn either blinking red or green. If the LED turns
                    blinking red, one of the optical fibers is faulty. Refer to Subsection 6.4.2 to isolate which
                    fiber is at fault. If the LED turns green, the optical fibers are good. Proceed to step 14 to
                    finish the test procedure.
                 15. At the DHU or supporting DEU, place the PORT ON/OFF switch in the OFF position
                     (press O).
                 16. Disconnect the loopback and the optical adapters from the optical fiber connectors.
                 17. Place a dust cap over the connector for each optical fiber
                18. Remove the dust plug from the DRU optical port or remote DEU host port.
                 19. Plug the loopback into the DRU optical port or DEU host port as shown in Figure 27.
                 20. If testing a DRU that is powered by the DHU or by a supporting DEU, place the PORT
                     ON/OFF switch in the ON position (press I).


Page 50
© 2002, ADC Telecommunications, Inc.


                                                                  ADCP-75-136 • Issue 1 • November 2002




                                  OPTICAL LOOPBACK
                                  CONNECTION DETAIL




                                                                                      17282-A




                                                    OPTICAL
                                                  TRANSCEIVER
                                        OPTICAL
                                       LOOPBACK


                                 Figure 27. DRU Loopback Test


21. The DRU STATUS LED or DEU HOST LED will turn either blinking red or green. If
    the LED turns blinking red, the optical port is faulty and the optical transceiver must be
    replaced. If the LED turns green, the optical port is good.
22. At the DHU or supporting DEU, place the PORT ON/OFF switch in the OFF position
    (press O).
23. Remove the loopback from the DRU optical port or remote DEU host port.
24. Clean the optical fiber connectors and then reconnect the optical fibers to the DRU
    optical port or remote DEU host port.
25. At the DHU or supporting DEU, place the PORT ON/OFF switch in the ON position
    (press I).
26. Verify that the PORT OK/NOK LED turns green.

6.4.2   Optical Loss Test Procedure

A break in an optical fiber or a fault with the optical connector will interrupt communications
between linked components. Use the following procedure to isolate a problem with an optical
fiber or optical connector:

Danger: This equipment uses a Class 1 Laser according to FDA/CDRH rules. Laser radiation
can seriously damage the retina of the eye. Do not look into the ends of any optical fiber. Do
not look directly into the optical transceiver of any digital unit or exposure to laser radiation
may result. An optical power meter should be used to verify active fibers. A protective cap or
hood MUST be immediately placed over any radiating transceiver or optical fiber connector
to avoid the potential of dangerous amounts of radiation exposure. This practice also prevents
dirt particles from entering the transceiver or connector.

 1. Put on the IR filtering safety glasses.
 2. At the DHU or supporting DEU, place the PORT ON/OFF switch for the optical fiber to
    be tested in the OFF position (press O) if not already off.



                                                                                             Page 51
                                                                  © 2002, ADC Telecommunications, Inc.


ADCP-75-136 • Issue 1 • November 2002




                  3. Disconnect the optical connectors at the DHU or supporting DEU and at the
                     corresponding DRU or remote DEU.
                  4. Inspect the optical connectors. Verify that each connector is clean and that no scratches
                     or imperfections are visible on the fiber end. Clean and polish the optical connector if
                     necessary.
                  5. Connect a laser light source to one end of the first optical fiber and an optical power
                     meter to the other end.
                  6. Verify that the power loss is within specifications (8 dB loss) for the length of the fiber
                     installed. If the power loss is not within specifications, repair or replace the optical fiber
                     and/or connector per local practice.
                  7. Repeat steps 5 and 6 for the second optical fiber.
                  8. Reconnect the optical connectors at the DHU or supporting DEU and the corresponding
                     DRU or remote DEU.
                  9. At the DHU or supporting DEU, place the PORT ON/OFF switch for the fiber that was
                     tested in the ON position (press I).


                6.4.3     DC Power Test Procedure

                The DRU is powered by 34–48 Vdc power which is supplied through the RJ-45 connector.
                Power to the DRU may be supplied by the DHU, DEU, or by a 120 Vac to 48 Vdc power
                converter (available separately as an accessory item) plugged into a properly grounded 120
                Vac outlet. Use the following procedure to test the DC power cable:
                  1. Disconnect the DC power cable from the DRU.
                  2. Connect the RJ-45 circuit access tool to the DRU as shown in Figure 28.




                                                          POWER
                                                           PORT




                                                                                                         17284-A




                                                     RJ-45 CIRCUIT
                                                     ACCESS TOOL

                                     POWER
                                   CONNECTOR


                                               Figure 28. Connect RJ-45 Circuit Access Tool



Page 52
© 2002, ADC Telecommunications, Inc.



Document Created: 2002-11-14 21:45:24
Document Modified: 2002-11-14 21:45:24

© 2024 FCC.report
This site is not affiliated with or endorsed by the FCC