INSTALLATION GUIDE
V1.5


Openpath Access Control System Installation Guide
    GETTING STARTED
    ADDITIONAL RESOURCES
    PRIOR TO INSTALLATION
Installation
    NETWORK REQUIREMENTS
    SELECTING A BACKUP BATTERY
    MOUNTING INSTRUCTIONS
    RECOMMENDED CONFIGURATION
         WIRING WITH THE 12/24V POWER SUPPLY
         WIRING THE REX WITH THE DOOR STRIKE
         WIRING THE REX WITH THE ELECTROMAGNETIC LOCK
         WIRING FAIL SAFE AND FAIL SECURE LOCKING HARDWARE
         WIRING TO LEGACY PANELS
         WIRING THE OPENPATH ELEVATOR BOARD
Troubleshooting
    LEGACY WIRING
    ACU LEDS
    READER LEDS
    RESETTING THE ACU
    PROVISIONING THE ACU
Regulatory
    UL
    CAN/ULC 60831-11-1-16 GRADE 1
    FCC
    IEC 62368-1
Warnings




 Version 1.5                           ©​ Openpath 2019      Page 2


Openpath Access Control System Installation Guide
   GETTING STARTED

   This Installation Guide explains how to install and configure Openpath Smart Hubs (ACUs) and
   Openpath Smart Readers as part of an Openpath Access Control system.


   ADDITIONAL RESOURCES

   ●    Smart Reader Data Sheet
   ●    Smart Hub (ACU) Data Sheet
   ●    Elevator Board Data Sheet


   PRIOR TO INSTALLATION

   Prior to installing Openpath hardware, it is assumed that you have performed a customer site
   survey and have determined the following:

   ●    How many entries need to be configured (e.g. doors, gates, and/or elevator floors)
   ●    Whether you’re using legacy wiring or new wiring
   ●    What kind of electronic entry mechanisms, Request to Exit (REX) mechanisms, and door
        contact sensors will be used and their power requirements. If your locking hardware requires
        24V, either use the Smart Hub ACU with included 24V power supply (OP-4ESH-24V) or use a
        separate 24V supply.
            ○ NOTE:​ The Smart Hub ACU with 12V power supply (OP-4ESH-12V) supports up to 2A for
                 locking hardware.
   ●    Whether you’re providing backup batteries for the ACUs. See ​SELECTING A BACKUP BATTERY​.
   ●    Whether you’re supporting a legacy access control panel. See ​WIRING TO LEGACY PANELS​.


Installation
   NETWORK REQUIREMENTS

   An Ethernet connection with DHCP must be used to connect the ACU to the Local Area Network
   (LAN). You also need to configure firewall settings to communicate with the Openpath system.
   Openpath uses the following outbound ports:

   ●    TCP port 443
   ●    TCP port 80
   ●    UDP port 123



Version 1.5                                ©​ Openpath 2019                                   Page 3


   NOTE:​ If using an external DNS server, outbound UDP port 53 must also be open.
   To support Wi-Fi unlocking from the mobile app, the Smart Hub’s inbound TCP port 443 must be
   available from within the LAN. Inbound port forwarding on the router, firewall, or NAT device is not
   required.


   SELECTING A BACKUP BATTERY

   While not required, Openpath recommends having a backup battery in the case of power outages.
   The size of battery depends on your setup and how long you want to power the system.

                                  Table 1:​ Power requirements (12V)
                             Smart Hub ACU           1A

                             Smart Reader            0.25A

                             Locking hardware        0.25A–0.5A
                             (while engaged)


   Assuming a 12V power supply, a Smart Hub ACU configured with four Openpath readers and
   locking hardware uses 4 Amps. To keep the system running for 3 hours with all entries engaged,
   you’d need 4A x 3 hours = 12 AH, so a 12V 12AH sealed lead acid (SLA) or gel cell battery.

   NOTE:​ For a 24V power supply, you need two 12V SLA or gel cell batteries in series.


   MOUNTING INSTRUCTIONS

   For a UL Listed System, the Smart Hub ACU must be mounted in a LifeSafety Power E1 enclosure
   with an FPO75 supply.

   To mount the enclosure:
   1. (Optional) Remove the enclosure’s cover.
   2. Locate the top keyhole mounting holes in the back of the enclosure.
   3. Mark and pre-drill the locations for the keyholes in the mounting surface.
   4. Partially install two fasteners appropriate for the surface on which the enclosure is being
      installed. Leave the heads of the fasteners approximately ¼" out from the surface. Minimum
      fastener size should be #10 or larger.
   5. Hang the enclosure on the two fasteners and mark the locations of the remaining mounting
      holes.
   6. Remove the enclosure and pre-drill the locations for the remaining mounting holes.
   7. Re-hang the enclosure on the top mounting fasteners, install the remaining fasteners and
      tighten all fasteners.



Version 1.5                                 ©​ Openpath 2019                                     Page 4


   8. Reinstall the enclosure’s cover, if removed in step 1.


      WARNING:​ Only connect the Controller Board to 12V. Over voltage can damage the board.


   To install a standalone Controller Board with 24V locking hardware:
   If you purchased the Controller Board separately and are using 24V locking hardware, we
   recommend using the LifeSafety Power E1 enclosure, FPO75 power supply (or FPV4 power supply),
   B100 secondary power supply, and C4 power control module.

   1. Follow all LifeSafety Power instructions for installing the FPO75 (or FPV4), B100, and C4 in the
      enclosure.
   2. Mount the Controller Board using the provided back plate.
   3. Connect the B100 secondary supply to the Controller Board.
      IMPORTANT:​ Verify that the jumper on the B100 is set to 12V.
   4. Mount the enclosure as detailed above.

                                   12/24V Smart Hub ACU Configuration




Version 1.5                                 ©​ Openpath 2019                                     Page 5


   To install a standalone Controller Board with 12V locking hardware:
   If you purchased the Controller Board separately and are using 12V locking hardware, we
   recommend using the FPV4-E1 power supply/enclosure.

   1. Follow all LifeSafety Power instructions for installing the power supply in the enclosure.
   2. Mount the Controller Board using the provided back plate.
   3. Connect the power supply to the Controller Board.
      IMPORTANT:​ Verify that the jumper on the FPV4 is set to 12V.
   4. Mount the enclosure as detailed above.

                                 12V Smart Hub ACU Configuration




Version 1.5                                 ©​ Openpath 2019                                       Page 6


   RECOMMENDED CONFIGURATION

   Openpath readers and ACUs communicate via RS-485. The following wire types are compatible,
   listed in the order of preference which impacts distance.

   ●    Shielded CAT6A (recommended, additional two pairs can be used for sensors)
   ●    Shielded CAT6
   ●    Shielded RS485 w/22-24AWG (lower gauge, thicker wire is better)
   ●    Shielded CAT5
   ●    Unshielded CAT6
   ●    Unshielded CAT5
   ●    Shielded 22/6
   ●    Unshielded 22/6

   Ideally, use one twisted pair for GND and VIN (power) and one twisted pair for +B and -A (data).

   For shielded wiring, connect one side of the drain wire (the shield around the wires) to the GND
   terminal on the ACU. Both the shield and the GND wire can share the same GND terminal. Do not
   connect the other side of the shield to anything.

   For standard reader installation, we recommend that you install a 1-Gang 20 CU box in order to
   flush-mount the reader. Alternatively, the reader may also be surface mounted with the included
   back plate.

   NOTE: ​For elevators, all relays and readers must be connected to the same ACU. If you need more
   than four access controlled floors or readers, add the Openpath Elevator Expansion Module.




Version 1.5                                 ©​ Openpath 2019                                     Page 7


                                                                                                                                                                              openpath


      24V SUPPLY                                UP TO 2A @ 12V DC and 1A @ 24V DC FOR LOCKING HARDWARE
                                                The Main Output can be switched by the Fire Alarm Interface (FAl).
                                                *If FAl control of both door strikes and electromagnetic locks is required, use the C4 Power Control Module.
           0
           O
           O    FIRE ALARM
           O    INTERFACE (FAl)
           O
           0    INPUT                                                                      ~
                                                                                           €]         +12V ONLY       D    D                          es]      NC        O
                                                                                           |||   O    GND
                                                                                                                     POWER
                                                                                                                      LEDs
                                                                                                                                                      e_)'E         C    0
                                                                                                                                                      *®       No        0A
                                                                                                                                                —D
                                                                                                 o    GND
                                                                                                 8    IN      *      a                                E        nc        O \
       |   o
           C p                                                                                        GND            hed                              y             C    G

      + EE                                                       REX                             21   .       ~
                                                                                                                                                                                        +    24V FAIL
           1A                 MAIN DC                                                            OA   snp                                       [     @        No]|      & ”
                                                                                                                                                                        —I                   SECURE
                              ouTPUT                                   No                   o         Jn      __"_   a             reLAY __|          m        NC]||     O
                                                                                                                                                                                              DOOR
                                                                                                                                                                                              STRIKE
                               + —                            NC \O    o                   0          eno     _      ®              LEDs              'fi          cl|    0
                                                                                            | O       IN                                              —<
                               |          I_                      C                                                                             ——o   M        NO        0o

                                                                                                                                                      7        NC        C |            +    A12V FAIL
      B100 SECONDARY SUPPLY                                                                      0    GND            o                                m                    ||
                                                                                                 o    m       p      2     []] sTATUS LED             ®             c    o             |——| SAFE MAG
                                                                                                                                                                                 omm    =     LOCK
                                                                DOOR                             O    enp            >                                =—       no||      0 \
                                                               CONTACT                           0    n       w#     o                          —D
                                                                                                                                                                                  FAIL SECURE hardware
                                                                                                 8    SNP     .      3           mcu reset @                                      locks when power is
                                                                                                 O    N              2             BUTTON                     iv||       0        interrupted
                                                                                            —0        m       _7     9
                               12v our1                                                                                                               P&A     srr||
                                                                                                                                                               o)        0
                                                                                                                                                                         o        FAIL SAFE hardware
                                                                                                 O
                                   _ | + |                                                       0    a12¥    _
                                                                                                              E                                       3
                                                                                                                                                      2        po||1     O        unlocks when power is
                                      |   |                                                      o    B       a                                               GND        0A       interrupted
                                                                                                 O    GND     &                                               12V        O
                                                                                                                                                      2       isp        O
                                                                                                                                                                                  Please refer to third
      C4 POWER CONTROL MODULE                                                                                                                         RA      srr|l|     o        party locking hardware
     *See note above                                           WIEGAND                                                                                2        o1        o        wiring instructions.

                               UOOR                                                              $s §                                                         ae) o
                         DI:II:I                               READER                            ao   1¥       a                                      9        po||      O
                                                                                                 o    )B      m                READER                                    3        NOTE: If locking
                                           Y¥                     T                              O    GND                      POWER                          12V                 hardware uses 12V,
                               D I:I D                            i Optional                                  _       0—       LEDs                   g       LED        O        use the C4 Power
                               DDD                                : Wiegand                      o    12v     &                                       g       BZR        O        Control Module.
                                                                  i Reader                                    3
                               toUTPUTS 1—4                       | connection                   Cl           §                                       8        ob        8        Make sure to set the
                                                                                                                                                                                  appropriate jumper
           ‘DD”ODHOD”OH‘                                          ;                              O    cnp     ra                        ADMIN         ~       anp        o        to 12V.
                                                                                 orange     o         |i~      za     A             BUTTON 0          <       i¥         O
tThe voltage of each C4 output                               openpath            ::fl:t     H o        ||a     &                                       m °)\              O
can be selected individually as                                READER            Gray       O         B       zo                                      S       Bé?        8
12V or 24V using the yellow                                                                “_0        GNP     __=                                     S        oo        0
jumper (indicated above)                                                                                                           Board—to—board     >
JcorrE'spt:unt:ling to the output:*                                                       [—| (DHCP Required)
                                                                                                             oi                    USB|—|
                                                                                                                                       connector              snp        8
position 1 on the jumper pins
is 24V (this is the default
setting) and position 2 is 12V.


   WIRING THE REX WITH THE DOOR STRIKE




Version 1.5                    ©​ Openpath 2019   Page 9


   WIRING THE REX WITH THE ELECTROMAGNETIC LOCK




Version 1.5                   ©​ Openpath 2019    Page 10


WIRING FAIL SAFE AND FAIL SECURE LOCKING HARDWARE

Fail safe and fail secure are ways of configuring locking hardware:
     ● Fail safe​ hardware ​unlocks​ when power is interrupted
     ● Fail secure​ hardware ​locks​ when power is interrupted




 Version 1.5                                 ©​ Openpath 2019         Page 11


   WIRING TO LEGACY PANELS

   To support a legacy access control system, install the ACU between the Openpath readers and the
   legacy panel, with the ACU Wiegand port configured as output to the legacy panel. Replace low
   frequency (LF) Wiegand readers with LF Openpath readers and high frequency (HF) Wiegand
   readers with HF Openpath readers. In this setup, the legacy panel controls all locking hardware and
   entry mechanisms while the Openpath system allows you to use the Openpath mobile app, Smart
   reader, and Touch functionality.




Version 1.5                                ©​ Openpath 2019                                   Page 12


   WIRING THE OPENPATH ELEVATOR EXPANSION MODULE




Version 1.5                  ©​ Openpath 2019      Page 13


Troubleshooting
   LEGACY WIRING
   ACU LEDS
   READER LED
   PROVISIONING THE ACU
   RESETTING THE ACU


   LEGACY WIRING

   Sometimes legacy wiring (unshielded and straight through, rather than shielded twisted pair, often
   22-6) results in slower connections and dropped packets between the Openpath Reader and Smart
   Hub. To remedy this, you can switch GND and VIN with +B and -A connections on the ACU and
   readers to ensure the data pair (+B and -A) are using the alternate pair of legacy wires.


   ACU LEDS




   The Openpath ACU has several LEDs that indicate the following:

   ●    POWER LEDs indicate that the ACU is connected to power



Version 1.5                                ©​ Openpath 2019                                  Page 14


   ●    The four RELAY LEDs indicate when the relays are activated
   ●    The STATUS LED in the center of the ACU indicates that the ACU has been configured with
        firmware. It will flash green when ​Identify​ is pressed in the Control Center.
   ●    The four READER POWER LEDs indicate that the ACU has output power enabled per reader


   READER LEDS

   The Openpath Smart Reader’s LEDs indicate the following:

   ●    If the center dot is solid white, then the door is locked
   ●    If the outer ring is solid white, then the door is unlocked
   ●    If the center dot quickly switches between multiple colors and outer ring quickly spins once,
        the reader has just received power
   ●    If all lights are off, the reader is not connected to power (check to see if the power wires are
        swapped)
   ●    If the center dot is flashing red, the reader is connected to power but cannot communicate with
        the ACU (check to see if the +B [blue] and -A [violet] lines are swapped)
   ●    If the center dot is solid blue, the reader is connected to power and can communicate with the
        ACU, but has not been configured as an entry in the Control Center
   ●    If the center dot is solid green, and the outer ring lights up and spins, that means the reader has
        been ​Identified​ via the Control Center
   ●    If the center dot is solid purple and the outer ring is solid white, the reader is possibly not
        receiving enough voltage or current, potentially due to a break in wiring – try connecting the
        reader directly to the ACU, bypassing any wire runs
   ●    If the center dot is solid pink and the outer ring is solid white, check that +12V IN (orange)
        hasn’t been swapped with +B (blue) or -A (violet)


   RESETTING THE ACU

   Soft Reset:​ To soft reset the ACU, disconnect power from the ACU, wait 10 seconds, then reconnect
   the power.


       WARNING:​ Only hard reset the ACU if absolutely necessary and if instructed by Openpath. This
       will clear all of the data off of the ACU and will require reprovisioning, which requires having a
       computer or mobile phone on the same network as the ACU.


   Hard Reset:​ To hard reset the ACU, disconnect power from the ACU, hold down the ADMIN
   BUTTON, reconnect power to the ACU, wait 20 seconds while still holding the button down, then
   release the button. Wait 10 minutes before re-provisioning the ACU following the ​PROVISIONING
   THE ACU​ steps below.




Version 1.5                                   ©​ Openpath 2019                                      Page 15


   PROVISIONING THE ACU

   Provisioning the ACU means registering it in the online portal and getting it up and running with
   the latest firmware. ACUs are shipped already provisioned, but below are instructions for this
   process in the case of ​RESETTING THE ACU​.

   To provision the ACU:
   1. Connect the ACU to the Internet via Ethernet
   2. Press the ADMIN BUTTON
   3. On a computer or mobile phone on the same network as the ACU, go to
       https://control.openpath.com
   4. Log in with your administrative login
   5. Go to ​Hardware​ > ​ACU Management
   6. Locate the ACU on the list and click ​Register
   7. A new window will open with instructions on registering the ACU. Click ​Yes​ to proceed.




Version 1.5                                ©​ Openpath 2019                                      Page 16


Regulatory
   All national and local electrical codes apply.


UL 294
   When the Openpath Smart Hub 4 Door Controller is enclosed in the E1 enclosure and powered by
   FPO75, the following performance levels are defined for the access control unit as per UL 294:

   Attack:                                               Level I
   Endurance:                                            Level I
   Line Security:                                        Level I
   Standby:                                              Level I
   Single Point Locking Device with Key Locks:           Level I

CAN/ULC 60831-11-1-16 GRADE 1
   For C-UL Listed applications, the unit shall be installed in accordance with Part 1 of the Canadian
   Electrical Code.


FCC
   This device complies with part 15 of the FCC Rules. Operation is subject to the following two
   conditions: (1) This device may not cause harmful interference, and (2) this device must accept any
   interference received, including interference that may cause undesired operation. To comply with
   FCC RF exposure compliance requirements, a separation distance of at least 20 cm should be
   maintained between the antenna of Openpath Smart Reader(s) and persons during operation.

   NOTE: This equipment has been tested and found to comply with the limits for a Class A digital
   device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable
   protection against harmful interference when the equipment is operated in a commercial
   environment. This equipment generates, uses, and can radiate radio frequency energy and, if not
   installed and used in accordance with the instruction manual, may cause harmful interference to
   radio communications. Operation of this equipment in a residential area is likely to cause harmful
   interference in which case the user will be required to correct the interference at his own expense.


IEC 62368-1
   ●    This equipment is intended only for use in a restricted access area.
   ●    Securely fasten the equipment according to LifeSafety Power mounting instructions. See
        FlexPower Vantage Standard Power System - Installation Manual​.
   ●    PROTECTIVE EARTHING: For safety, the Smart Hub must only be plugged into a grounded
        3-prong outlet, wired with a minimum of 16 gauge wire to ground.




Version 1.5                                  ©​ Openpath 2019                                   Page 17


Warnings
   ●    Disconnect power before servicing
   ●    Do not plug into an outlet controlled by an on/off switch
   ●    Powering power supply with 230V requires jumper modification, see power supply data sheet
        for more information




Version 1.5                               ©​ Openpath 2019                                 Page 18


Technical Specifications

    Smart Hub with 12/24V Supply (OP-SH-24V)       120V, 0.7A or 230V, 0.3A, 50/60 Hz

    Smart Readers (OP-RLF-STD, OP-RHF-STD,         12VDC, 0.25A
    OP-RLF-MULB, OP-RHF-MULB)                      OP-RLF-STD/MULB: FCC ID: 2APJVOPRLF
                                                   OP-RHF-STD/MULB: FCC ID: 2APJVOPRHF

    Standalone ACU Board (OP-4ECTR)                10-14VDC, 1A

    Elevator Board (OP-16EM)                       12-24VDC, 0.35A




Version 1.5                             ©​ Openpath 2019                                Page 19