User Manual

FCC ID: 2AP4G-FS-SNS-02

Users Manual

Download: PDF
FCCID_4087201

s




    EkkoHub        and     EkkoSensors
    Installation and User Manual




                             Version 0.1 – 18th July 2018


                             EkkoHub and EkkoSensors Installation and User Manual


Contents
1.       DOCUMENT INFORMATION .......................................................................................................................... 2
     1.1.        INTRODUCTION ................................................................................................................................................ 2
     1.2.        DISCLAIMER..................................................................................................................................................... 2
2.       SENSOR INSTALLATION ................................................................................................................................. 3
     2.1.     SENSOR TYPES .................................................................................................................................................. 3
     2.2.     STANDARD RACKS ............................................................................................................................................. 4
        2.2.1.     Wireless Sensor - single ....................................................................................................................... 5
        2.2.2.     Wireless Sensor - dual ......................................................................................................................... 6
        2.2.3.     Wireless Sensor - alternative .............................................................................................................. 7
     2.3.     OTHER RACK TYPES & INSTALLATIONS .................................................................................................................. 8
        2.3.1.     Glass Front Racks ................................................................................................................................ 8
        2.3.2.     Mixed Inlet Racks ................................................................................................................................ 8
3.       HUB V2 INSTALLATION .................................................................................................................................. 9
     3.1.        MOUNTING METHOD ........................................................................................................................................ 9
     3.2.        CONNECTIONS ................................................................................................................................................. 9
     3.3.        STATUS LEDS ................................................................................................................................................ 10
4.       REGULATORY INFORMATION .......................................................................................................................10



REVISION HISTORY

 Version                    Notes
 V0.1                       First version




EkkoSense Ltd Registered in England and Wales No. 8594313 Tower House, Lucy Tower Street, Lincoln,
LN1 1XW
                                                                                              1


                 EkkoHub and EkkoSensors Installation and User Manual


1. Document Information

   1.1. Introduction
This document contains the standards for hardware installation and configuration.

This document is for installers.

These standards are followed in all EkkoSense installations unless otherwise specified and agreed.


   1.2. Disclaimer
THIS DOCUMENT IS FOR INFORMATIONAL PURPOSES ONLY. THIS DOCUMENT IS PROVIDED “AS IS” WITH
NO WARRANTIES WHATSOEVER, INCLUDING ANY WARRANTY OF MERCHANTABILITY, NON-
INFRINGEMENT, FITNESS FOR ANY PARTICULAR PURPOSE, OR ANY WARRANTY OTHERWISE ARISING OUT
OF ANY PROPOSAL, SPECIFICATION OR SAMPLE.



Ekkosense disclaims all liability, including liability for infringement of any proprietary rights, relating to
use of information in this specification.

No license, express or implied, to any intellectual property rights is granted herein.



The information in this document relates to EkkoSoft Critical v3.2+




EkkoSense Ltd Registered in England and Wales No. 8594313 Tower House, Lucy Tower Street, Lincoln,
LN1 1XW
                                                                                              2


                 EkkoHub and EkkoSensors Installation and User Manual


2. Sensor Installation
   2.1. Sensor types
Sensor functionality is identified by the part number:

      Frequency of operation                   Functionality code                 Hardware version
           ES (868MHz)                -                                   -
                                                   See below                         Currently 02
           FS (915MHz)


TSI    FS-TSI-02/ES-TSI-02 Wireless Temperature Sensor with internal measurement
TSX    FS-TSX-02/ES-TSX-02 Wireless Temperature Sensor with external and internal measurement
THI    FS-THI-02/ES-THI-02 Wireless Temperature and Relative Humidity Sensor with internal
measurement
THX    FS-THX-02/ES-THX-02 Wireless Temperature and Relative Humidity Sensor with internal
measurement and external only temperature measurement
THD    FS-THD-02/ES-THD-02 Wireless Temperature and Relative Humidity Sensor with internal
measurement and display of measured values
TDX    FS-TDX-02/ES-TDX-02 Wireless Temperature and Humidity Sensor with Display and external
temperature only measurement
All sensors include the functionality section of their part number in the barcode label:




Temperature only and Temperature and Humidity sensors can also be distinguished by the fact that the
Temperature and Humidity sensors have slots cut in the bottom of the sensor.




For simplicity in this document where sensors need to be distinguished by functionality they will be
identified by their functionality code only.



EkkoSense Ltd Registered in England and Wales No. 8594313 Tower House, Lucy Tower Street, Lincoln,
LN1 1XW
                                                                                              3


                 EkkoHub and EkkoSensors Installation and User Manual


   2.2. Standard Racks
This section indicates the EkkoSense standards for installing sensors on racks within data centre
environments. There are a number of different configurations depending on the sensors purchased and
client installation preferences.


The follow general principles apply to all variations:

          Sensors are to be installed on inlets only
          Wireless sensors should be fixed to glass front racks with Hi-Bond adhesive tape. This is
           supplied as standard on the sensors.
          Wireless sensors should be fixed to mesh front racks with a black cable tie using the holes in
           the back of the sensor. The Hi-Bond adhesive tape can be used to provide additional stability
           but must not be used as the primary method of attachment.
          Flylead (external) sensors should be securely fastened using black cable ties.
          In some cases, additional black tie-wraps may be required to fix the device in place
          Sensors should be positioned near equipment inlets in such a way that the inlet is not blocked




EkkoSense Ltd Registered in England and Wales No. 8594313 Tower House, Lucy Tower Street, Lincoln,
LN1 1XW
                                                                                              4


                EkkoHub and EkkoSensors Installation and User Manual


      2.2.1.   Wireless Sensor - single
Below is the standard installation for EkkoSense Critical Things sensors on equipment racks within data
centres. This applies to the following sensor types:

          Wireless Temperature only (TSI)
          Wireless Temperature + RH (THI)
          Wireless Temperature + RH + Display (THD)




EkkoSense Ltd Registered in England and Wales No. 8594313 Tower House, Lucy Tower Street, Lincoln,
LN1 1XW
                                                                                              5


                 EkkoHub and EkkoSensors Installation and User Manual


      2.2.2.    Wireless Sensor - dual
Below is the standard installation for EkkoSense Critical Things dual sensors on equipment racks within
data centres. This applies to the following sensor types:


          Wireless Temperature + Temperature flylead (TSX)
          Wireless Temperature + RH + Temperature flylead (THX)
          Wireless Temperature + RH + Display + Temperature flylead (TDX)




1.2m flylead variant                                           2.0m flylead variant (special order)




EkkoSense Ltd Registered in England and Wales No. 8594313 Tower House, Lucy Tower Street, Lincoln,
LN1 1XW
                                                                                              6


                 EkkoHub and EkkoSensors Installation and User Manual


      2.2.3.    Wireless Sensor - alternative
In some cases it may not be appropriate to install to the standards listed previously due to one of the
following reasons;


          Client does not wish to have wireless sensor case on display
          Sensor case does not have a fixing position on the front of the rack

In these cases, the sensor should be fixed to the top of the rack and a flylead sensor run down to the
monitoring locations as shown below.




Flylead sensor (hidden)                                    Dual Flylead sensor (hidden)

NOTE 1: The EkkoSoft application will assume a single flylead sensor is positioned as high inlet and low
inlet. This configuration will need to be adjusted when installing sensors so as not to give provide incorrect
readings into the application.


NOTE 2: The Dual Flylead sensor is not a standard offering and must be asked for on request – lead times
are 2-4 weeks.




EkkoSense Ltd Registered in England and Wales No. 8594313 Tower House, Lucy Tower Street, Lincoln,
LN1 1XW
                                                                                              7


                 EkkoHub and EkkoSensors Installation and User Manual


   2.3. Other Rack Types & Installations
In some data centres other rack types exist which affect the installation methodology.


      2.3.1.     Glass Front Racks
For these racks the airflow for the equipment is usually provided at the bottom of the rack, rather than
through the front.


If the airflow is predominantly provided at the base of the rack then a flylead sensor should be installed
so that the flylead sensor is located behind on the glass near to the equipment.


      2.3.2.     Mixed Inlet Racks
For mixed inlet racks it can be difficult to assess the best place for a sensor to be placed. The sensor should
be placed on the side of the rack where the uppermost piece of equipment has an inlet. This represents
the ‘worst-case’ inlet and is therefore the most critical.


In EkkoSoft, the rack should be indicated as mixed.




EkkoSense Ltd Registered in England and Wales No. 8594313 Tower House, Lucy Tower Street, Lincoln,
LN1 1XW
                                                                                              8


                 EkkoHub and EkkoSensors Installation and User Manual


3. Hub V2 installation

   3.1. Mounting method
The EkkoHub has four mounting holes concealed behind the flaps at the side of the unit:




These holes can be used with cable ties to fit the EkkoHub to cable baskets or to screw the EkkoHub to a
wall.

The EkkoHub can be installed in any orientation. The antenna is mounted internally behind the front panel
(with the label and status LEDs). When installing the EkkoHub ensure that this front panel is not positioned
on or adjacent to metal. For best performance ensure the body of the EkkoHub is in clear space with the
EkkoHub attached on its back face only.


   3.2. Connections
The EkkoHub has three external connections along one face:




             USB
                                    DC in 9-12V
                                    centre positive
                  Ethernet

The Ethernet port is the only one that is normally connected at installation, with power being supplied to
the EkkoHub using a Power over Ethernet switch. The USB port can be used to connect to a laptop for


EkkoSense Ltd Registered in England and Wales No. 8594313 Tower House, Lucy Tower Street, Lincoln,
LN1 1XW
                                                                                              9


                EkkoHub and EkkoSensors Installation and User Manual


changing the EkkoHub configuration. In this case the EkkoHub will draw power from the USB host device
and does not need the Ethernet connection.


   3.3. Status LEDs




 LED name                 Function and expected status
 Power                    Illuminates to indicate that the EkkoHub is receiving power. This must be
                          Illuminated for the hub to work. If the LED does not light then check the
                          cabling between the hub and the PoE switch and check that the PoE switch is
                          powered.
 Network                  Illuminates continuously to indicate that the EkkoHub has a connection to
                          EkkoSense servers. This must be Illuminated for the EkkoHub to work. If the
                          LED does not light then check the cabling to the PoE switch, check that the
                          PoE switch has a connection to external internet, check that there is no MAC
                          address filtering implemented, check that the EkkoHub has been configured
                          correctly.
 Transmit                 Status not currently relevant
 Receive                  Toggles state from dark to illuminated and vice versa every time a data packet
                          is received from a sensor. If there is no activity then check that the hub is
                          correctly configured for the sensors (PAN ID, Encryption Key).




4. Regulatory information
These devices comply with part 15 of the FCC Rules. Operation is subject to the following two conditions:

(1) This device may not cause harmful interference, and

(2) this device must accept any interference received, including interference that may cause undesired
operation.

CAUTION: Changes or modifications to the products that are not expressly approved by EkkoSense Ltd
could void the user’s authority to operate the equipment.