Test report

FCC ID: 2AG32EPB41211

Test Report

Download: PDF
FCCID_4255911

                          Shenzhen Zhongjian Nanfang Testing Co., Ltd.
                                                                                                  Report No: CCISE190309401

1        Cover Page

                                      FCC REPORT
Applicant:                                  Baicells Technologies Co., Ltd.
                                            3F, Hui Yuan Development Building, No.1 Shangdi Information
Address of Applicant:
                                            Industry Base, Haidian Dist., Beijing, China
Equipment Under Test (EUT)

    Product Name:                           Outdoor Smart UPS

    Model No.:                              EPB41211

FCC ID:                                     2AG32EPB41211

Applicable standards:                       FCC CFR Title 47 Part 15 Subpart B

Date of sample receipt:                     27 Mar., 2019

Date of Test:                               27 Mar., to 12 Apr., 2019

Date of report issued:                      15 Apr., 2019

Test Result:                                Pass *
  * In the configuration tested, the EUT complied with the standards specified above.




 Authorized Signature:




       Bruce Zhang
    Laboratory Manager
This report details the results of the testing carried out on one sample. The results contained in this test report do not relate to other
samples of the same product and does not permit the use of the CCIS product certification mark. The manufacturer should ensure that all
products in series production are in conformity with the product sample detailed in this report.

This report may only be reproduced and distributed in full. If the product in this report is used in any configuration other than that detailed in
the report, the manufacturer must ensure the new system complies with all relevant standards.

This document cannot be reproduced except in full, without prior written approval of the Company. Any unauthorized alteration, forgery or
falsification of the content or appearance of this document is unlawful and offenders may be prosecuted to the fullest extent of the law.
Unless otherwise stated the results shown in this test report refer only to the sample(s) tested and such sample(s) are retained for 90 days
only.


                                                                                 Report No: CCISE190309401

2      Version
       Version No.                           Date                                  Description
             00                         15 Apr., 2019                                Original




    Tested by:                                                           Date:          15 Apr., 2019

                                       Test Engineer

    Reviewed by:                                                         Date:          15 Apr., 2019

                                    Project Engineer




Shenzhen Zhongjian Nanfang Testing Co., Ltd.                                           Project No.: CCISE1903094
No. B-C, 1/F., Building 2, Laodong No.2 Industrial Park, Xixiang Road,
Bao’an District, Shenzhen, Guangdong, China
Telephone: +86 (0) 755 2311 8282 Fax: +86 (0) 755 2311 6366                                          Page 2 of 30


                                                                                                                            Report No: CCISE190309401

3         Contents
                                                                                                                                                                                 Page
1     COVER PAGE ....................................................................................................................................................... 1
2     VERSION ............................................................................................................................................................... 2
3     CONTENTS ........................................................................................................................................................... 3
4     TEST SUMMARY .................................................................................................................................................. 4
5     GENERAL INFORMATION .................................................................................................................................. 5
    5.1    CLIENT INFORMATION ...................................................................................................................................................... 5
    5.2    GENERAL DESCRIPTION OF E.U.T. ...................................................................................................................................... 5
    5.3    TEST MODE.................................................................................................................................................................... 5
    5.4    MEASUREMENT UNCERTAINTY ........................................................................................................................................... 5
    5.5    DESCRIPTION OF SUPPORT UNITS ....................................................................................................................................... 6
    5.6    RELATED SUBMITTAL(S) / GRANT (S) ................................................................................................................................... 6
    5.7    DESCRIPTION OF CABLE USED ............................................................................................................................................ 6
    5.8    LABORATORY FACILITY ...................................................................................................................................................... 6
    5.9    LABORATORY LOCATION ................................................................................................................................................... 6
    5.10      TEST INSTRUMENTS LIST ............................................................................................................................................... 7
6     TEST RESULTS AND MEASUREMENT DATA ................................................................................................ 8
    6.1    CONDUCTED EMISSION ..................................................................................................................................................... 8
    6.2    RADIATED EMISSION ...................................................................................................................................................... 11
7     TEST SETUP PHOTO ........................................................................................................................................ 17
8     EUT CONSTRUCTIONAL DETAILS ................................................................................................................ 19




Shenzhen Zhongjian Nanfang Testing Co., Ltd.                                                                                               Project No.: CCISE1903094
No. B-C, 1/F., Building 2, Laodong No.2 Industrial Park, Xixiang Road,
Bao’an District, Shenzhen, Guangdong, China
Telephone: +86 (0) 755 2311 8282 Fax: +86 (0) 755 2311 6366                                                                                                        Page 3 of 30


                                                                             Report No: CCISE190309401

4      Test Summary
                 Test Item                               Section in CFR 47                 Result
           Conducted Emission                                 Part 15.107                   Pass
            Radiated Emission                                 Part 15.109                   Pass
 Remark:
 Pass: The EUT complies with the essential requirements in the standard.
 N/A: The EUT not applicable of the test item.




Shenzhen Zhongjian Nanfang Testing Co., Ltd.                                      Project No.: CCISE1903094
No. B-C, 1/F., Building 2, Laodong No.2 Industrial Park, Xixiang Road,
Bao’an District, Shenzhen, Guangdong, China
Telephone: +86 (0) 755 2311 8282 Fax: +86 (0) 755 2311 6366                                     Page 4 of 30


c c I s                                                                            Report No: CCISE190309401

5       General Information
5.1 Client Information
        Applicant:                               Baicells Technologies Co., Ltd.
        Address:                                 3F, Hui Yuan Development Building, No.1 Shangdi Information
                                                 Industry Base, Haidian Dist., Beijing, China
        Manufacturer:                            Baicells Technologies Co., Ltd.
        Address:                                 3F, Hui Yuan Development Building, No.1 Shangdi Information
                                                 Industry Base, Haidian Dist., Beijing, China

5.2 General Description of E.U.T.
        Product Name:                            Outdoor Smart UPS
        Model No.:                               EPB41211
        Power supply:                            Model No.: 12S2P—B Battery Pack
                                                 Nominal Voltage: 43. 2V
                                                 Nominal Capacity: 5000mAh
                                                 Nominal Energy: 216Wh
                                                 Output Voitage Range: DC37V~DCS54V
                                                 Peak Output Power:=200W
        Test Sample Condition:                  The test samples were provided in good working order with no
                                                visible defects.

5.3 Test Mode
      Operating mode            Detail description
       Full load mode           Keep the EUT in Full load mode
 The sample was placed 0.8m above the ground plane of 3m chamber. Measurements in both horizontal and
 vertical polarities were performed. During the test, each emission was maximized by: having the EUT
 continuously working, investigated all operating modes, rotated about all 3 axis (X, Y & Z) and considered
 typical configuration to obtain worst position, manipulating interconnecting cables, rotating the turntable,
 varying antenna height from 1m to 4m in both horizontal and vertical polarizations. The emissions worst—case
 are shown in Test Results of the following pages.

5.4 Measurement Uncertainty
                    Parameters                                               Expanded Uncertainty
        Conducted Emission (9kHz ~ 30MHz)                                       +2.22 dB (k=2)
         Radiated Emission (@kHz ~ 3OMHz)                                       +2.76 dB (k=2)
       Radiated Emission (3OMHz ~ 1000MHz)                                      +4.28 dB (k=2)
         Radiated Emission (1GHz ~ 18GHz)                                       +5.72 dB (k=2)
        Radiated Emission (18GHz ~ 40GHz)                                       +2.88 dB (k=2)




Shenzhen Zhongjian Nanfang Testing Co., Ltd.                                             Project No.: CCISE1903094
No. B—C, 1/F., Building 2, Laodong No.2 Industrial Park, Xixiang Road,
Bac‘an District, Shenzhen, Guangdong, China
Telephone: +86 (0) 755 2311 8282 Fax: +86 (0) 755 2311 6366                                            Page 5 of 30


                                                                          Report No: CCISE190309401

5.5 Description of Support Units
      Manufacturer                Description                 Model      Serial Number        FCC ID/DoC
             /                 Cement Resistor           30W 5RJ/30RJ          /                    /

5.6 Related Submittal(s) / Grant (s)
       This is an original grant, no related submittals and grants.

5.7 Description of Cable Used
      N/A

5.8 Laboratory Facility
       The test facility is recognized, certified, or accredited by the following organizations:
        FCC - Registration No.: 727551
       Shenzhen Zhongjian Nanfang Testing Co., Ltd. has been accredited as a testing laboratory by FCC
       (Federal Communications Commission). The Registration No. is 727551.
        IC - Registration No.: 10106A-1
       The 3m Semi-anechoic chamber of Shenzhen Zhongjian Nanfang Testing Co., Ltd. has been
       Registered by Certification and Engineering Bureau of Industry Canada for radio equipment testing with
       Registration No.: 10106A-1.
        CNAS - Registration No.: CNAS L6048
       Shenzhen Zhongjian Nanfang Testing Co., Ltd. is accredited to ISO/IEC 17025:2005 General
       Requirements for the Competence of Testing and Calibration laboratories for the competence of testing.
       The Registration No. is CNAS L6048.
        A2LA - Registration No.: 4346.01
       This laboratory is accredited in accordance with the recognized International Standard ISO/IEC
       17025:2005 General requirements for the competence of testing and calibration laboratories. The test
       scope can be found as below link: https://portal.a2la.org/scopepdf/4346-01.pdf

5.9 Laboratory Location
       Shenzhen Zhongjian Nanfang Testing Co., Ltd.
       Address: No. B-C, 1/F., Building 2, Laodong No.2 Industrial Park, Xixiang Road,
       Bao’an District, Shenzhen, Guangdong, China
       Tel: +86-755-23118282, Fax: +86-755-23116366
       Email: info@ccis-cb.com, Website: http://www.ccis-cb.com




Shenzhen Zhongjian Nanfang Testing Co., Ltd.                                       Project No.: CCISE1903094
No. B-C, 1/F., Building 2, Laodong No.2 Industrial Park, Xixiang Road,
Bao’an District, Shenzhen, Guangdong, China
Telephone: +86 (0) 755 2311 8282 Fax: +86 (0) 755 2311 6366                                      Page 6 of 30


                                                                                  Report No: CCISE190309401

5.10 Test Instruments list
 Radiated Emission:
                                                                                           Cal. Date        Cal. Due date
    Test Equipment            Manufacturer             Model No.          Serial No.
                                                                                          (mm-dd-yy)         (mm-dd-yy)
        3m SAC                  SAEMC                  9m*6m*6m               966         07-22-2017         07-21-2020
     Loop Antenna            SCHWARZBECK              FMZB1519B             00044         03-18-2019         03-17-2020
   BiConiLog Antenna         SCHWARZBECK               VULB9163               497         03-18-2019         03-17-2020
     Horn Antenna            SCHWARZBECK              BBHA9120D               916         03-18-2019         03-17-2020
     Horn Antenna            SCHWARZBECK              BBHA9120D              1805         06-22-2017         06-21-2020
     Horn Antenna            SCHWARZBECK              BBHA 9170          BBHA9170582      11-21-2018         11-20-2019
   EMI Test Software             AUDIX                    E3                           Version: 6.110919b
     Pre-amplifier                 HP                   8447D            2944A09358       03-18-2019         03-17-2020
     Pre-amplifier                 CD                  PAP-1G18             11804         03-18-2019         03-17-2020
   Spectrum analyzer         Rohde & Schwarz            FSP30              101454         03-18-2019         03-17-2020
   Spectrum analyzer         Rohde & Schwarz            FSP40              100363         11-21-2018         11-20-2019
   EMI Test Receiver         Rohde & Schwarz           ESRP7                101070        03-18-2019         03-17-2020
        Cable                    ZDECL              Z108-NJ-NJ-81          1608458        03-18-2019         03-17-2020
        Cable                 MICRO-COAX              MFR64639             K10742-5       03-18-2019         03-17-2020
        Cable                   SUHNER              SUCOFLEX100           58193/4PE       03-18-2019         03-17-2020


 Conducted Emission:
                                                                                         Cal. Date          Cal. Due date
   Test Equipment             Manufacturer            Model No.           Serial No.
                                                                                        (mm-dd-yy)           (mm-dd-yy)
  EMI Test Receiver         Rohde & Schwarz             ESCI               101189       03-18-2019           03-17-2020
    Pulse Limiter           SCHWARZBECK              OSRAM 2306             9731        03-18-2019           03-17-2020
        LISN                    CHASE                 MN2050D               1447        03-18-2019           03-17-2020
        LISN                Rohde & Schwarz           ESH3-Z5            8438621/010    07-21-2018           07-20-2019
       Cable                      HP                   10503A                N/A        03-18-2019           03-17-2020
  EMI Test Software             AUDIX                    E3                          Version: 6.110919b




Shenzhen Zhongjian Nanfang Testing Co., Ltd.                                                Project No.: CCISE1903094
No. B-C, 1/F., Building 2, Laodong No.2 Industrial Park, Xixiang Road,
Bao’an District, Shenzhen, Guangdong, China
Telephone: +86 (0) 755 2311 8282 Fax: +86 (0) 755 2311 6366                                                  Page 7 of 30


                                                                               Report No: CCISE190309401

6      Test results and Measurement Data
6.1 Conducted Emission
        Test Requirement:               FCC Part 15 B Section 15.107
        Test Method:                    ANSI C63.4:2014
        Test Frequency Range:           150kHz to 30MHz
        Class / Severity:               Class A                  Class B
        Receiver setup:                 RBW=9kHz, VBW=30kHz
        Limit:                                                                          Limit (dBµV)
                                          Frequency range (MHz)
                                                                           Quasi-peak                  Average
                                                   0.15-0.5                   79                         66
                                                    0.5-30                    73                         60
        Test setup:




        Test procedure                  1. The E.U.T and simulators are connected to the main power through a
                                           line impedance stabilization network(L.I.S.N.). The provide a
                                           50ohm/50uH coupling impedance for the measuring equipment.
                                        2. The peripheral devices are also connected to the main power through a
                                           LISN that provides a 50ohm/50uH coupling impedance with 50ohm
                                           termination. (Please refers to the block diagram of the test setup and
                                           photographs).
                                        3. Both sides of A.C. line are checked for maximum conducted
                                           interference. In order to find the maximum emission, the relative
                                           positions of equipment and all of the interface cables must be changed
                                           according to ANSI C63.4: 2014 on conducted measurement.
        Test Instruments:               Refer to section 5.9 for details
        Test mode:                      Refer to section 5.3 for details
        Test results:                   Pass




Shenzhen Zhongjian Nanfang Testing Co., Ltd.                                             Project No.: CCISE1903094
No. B-C, 1/F., Building 2, Laodong No.2 Industrial Park, Xixiang Road,
Bao’an District, Shenzhen, Guangdong, China
Telephone: +86 (0) 755 2311 8282 Fax: +86 (0) 755 2311 6366                                              Page 8 of 30


c c I s                                                                                Report No: CCISE190309401

Measurement data:
Product name:                 Outdoor Smart UPS                 Product model:             EPB41211

Test by:                      Carey                             Test mode:                 Full load mode

Test frequency:                150 kHz ~ 30 MHz                 Phase:                     Line

Test voltage:                 AC 120 V/60 Hz                    Environment:               Temp: 22.5°C          Huni: 55%


   100 Level (dBuV)


     90

     80
                                                                                                       FCC PART15 A OP
     70
     60                                                                                                FCC PARJ4 71 5 A AV
                                                                                                                i2
     50

    40|\                                                                                                             \
                                                                                                                         \



     20                                                                                                                      "wntl
     10

          A5   .2                  6              1            2                   5              10             20              30
r.... 44                                                 Frequency (MHz)

                            Read    LISN    Cable             Linit      Over
                    Freq   Level Factor      Loss     Level    Line   Limit Remark

                     MHz    dBu¥       dB      dB      dBu¥    dBu¥        dB

    1           0.162      44.13   —O.44    10.77     54.46   19.00 —24.54 QP
    2           0.166      34.55   —O.44    10.77     44.88   66.00 —21.12 Average
    3           0.214      40.97   —O.41    10.76     §1.32   19.00 —27.68 qP
    4           0.214      33.36   —O.41    10.76     43.71   66.00   —22.29    Average
    5           0.410      29.47   —O.37    10.72     39.82   66.00   —26.18    Average
    6           0.579      38.03   —0.39    10.76     48.40   73.00   —24.60    qP
    i           0.T27T     42.63   —0.38    10.78     §3.03   13.00   —19.97    9P
    8           0.731      34.30   —0.38    10.78     44.70   60.00   —15.30    Average
    9           3.364      37.33   —0.45    10.91     47.79   60.00   —12.21    Average
   10           3.528      46.08   —0.45    10.90     56.53   73.00   —16.47    9P
   11          19.428      48.98   —0.94    10.95     58.97   T3.00   —14.03    QP
   12          19.428      41.08   —0.94    10.93     51.07   60.00    —8.93    Average




Notes:
1. An initial pre—scan was performed on the line and neutral lines with peak detector.
2. Quasi—Peak and Average measurement were performed at the frequencies with maximized peak emission.
3. _Final Level =Receiver Read level + LISN Factor + Cable Loss.




Shenzhen Zhongjian Nanfang Testing Co., Ltd.                                                 Project No.: CCISE1903094
No. B—C, 1/F., Building 2, Laodong No.2 Industrial Park, Xixiang Road,
Bac‘an District, Shenzhen, Guangdong, China
Telephone: +86 (0) 755 2311 8282 Fax: +86 (0) 755 2311 6366                                                      Page 9 of 30


c c I s                                                                                                       Report No: CCISE190309401


Product name:                          Outdoor Smart UPS                                Product model:            EPB41211

Test by:                               Carey                                            Test mode:                Full load mode

Test frequency:                        150 kHz ~ 30 MHz                                 Phase:                    Neutral

Test voltage:                          AC 120 V/60 Hz                                   Environment:              Temp: 22.5°C      Huni: 55%


   100 Level (dBuV)

    90

    80
                                                                                                                            FCC PART1S A OP
    70
    6013                                                                                                                    FCC PART15 A AV
          |                                              68

    T "i‘            ;                                   e|
    »      i
    30 | fl' .
                         .     i    W IWY
                                   ‘ \
                                        M                           J
              [ I             | J |                 |         |
    20|         |}                 |               1H
    10

          16 12                               :5                    1               2                     5           10            20        30
¥e... Sm                                                                     Frequency (MHz)


                                    Read   LISN               Cable                     Limit     Over
                         Freq      Level Factor                 Loss       Level         Line    Linit Remark

                             NBz       dBu?             dB              dB _dBu¥y        dBu¥        dB           C
      1                  0.154     49.49           —D.68          10.78     59.59       79.00 —19.41 qP
      2                  .154      38.73           —0.68          10.78    48.83        66.00 —17.17 Average
      3                  0.162     45.99           —D.68          10.77     56.08       79.00 —22.92 qP
      4                  0.211     34.38           —0.68          10.76    44.46        66.00 —21.54 Average
      5                  0.386     30.57           —0.64          10.72    40.65        66.00 —25.35 Average
      6                  .712      42.23           —D.64          10.78     §2.37       73.00 —20.63 9P
      i                  0.727     32.93           —0.64          10.78    43.07        60.00 —16.93 Average
      8                  .783      42.35           —0.64          10.81     §2.52       73.00 —20.48 QP
      9                  3.364     43.34           —0.68          10.91     53.57       73.00 —19.43 9P
     10                  3.364     35.02           —0.68          10.91    45.25        60.00 —14.75 Average
     1               16.486        48.52           —1.01          10.91     58.42       73.00 —14.58 qP
     12              18.135        37.88           —1.21          10.92    47.59        60.00 —12.41 Average



Notes:
1. An initial pre—scan was performed on the line and neutral lines with peak detector.
2. Quasi—Peak and Average measurement were performed at the frequencies with maximized peak emission.
3. _Final Level =Receiver Read level + LISN Factor + Cable Loss.




Shenzhen Zhongjian Nanfang Testing Co., Ltd.                                                                        Project No.: CCISE1903094
No. B—C, 1/F., Building 2, Laodong No.2 Industrial Park, Xixiang Road,
Bac‘an District, Shenzhen, Guangdong, China
Telephone: +86 (0) 755 2311 8282 Fax: +86 (0) 755 2311 6366                                                                        Page 10 of 30


                                                                           Report No: CCISE190309401

6.2 Radiated Emission
        Test Requirement:             FCC Part 15 B Section 15.109
        Test Method:                  ANSI C63.4:2014
        Test Frequency Range:         30MHz to 6000MHz
        Class / Severity:             Class A                    Class B
        Test site:                    Measurement Distance: 3m (Semi-Anechoic Chamber)
        Receiver setup:                 Frequency       Detector        RBW      VBW           Remark
                                      30MHz-1GHz       Quasi-peak      120kHz   300kHz    Quasi-peak Value
                                                         Peak           1MHz     3MHz        Peak Value
                                       Above 1GHz
                                                         RMS            1MHz     3MHz      Average Value
        Limit:                               Frequency           Limit (dBuV/m @3m)          Remark
                                           30MHz-88MHz                    49.0           Quasi-peak Value
                                          88MHz-216MHz                    53.5           Quasi-peak Value
                                          216MHz-960MHz                   56.4           Quasi-peak Value
                                           960MHz-1GHz                    59.5           Quasi-peak Value
                                                                          59.5            Average Value
                                            Above 1GHz
                                                                          79.5             Peak Value
        Test setup:                   Below 1GHz




                                      Above 1GHz




Shenzhen Zhongjian Nanfang Testing Co., Ltd.                                     Project No.: CCISE1903094
No. B-C, 1/F., Building 2, Laodong No.2 Industrial Park, Xixiang Road,
Bao’an District, Shenzhen, Guangdong, China
Telephone: +86 (0) 755 2311 8282 Fax: +86 (0) 755 2311 6366                                    Page 11 of 30


                                                                               Report No: CCISE190309401


       Test Procedure:                  1. The EUT was placed on the top of a rotating table 0.8 meters above
                                           the ground at a 3 meter semi-anechoic camber. The table was rotated
                                           360 degrees to determine the position of the highest radiation.
                                        2. The EUT was set 3 meters away from the interference-receiving
                                           antenna, which was mounted on the top of a variable-height antenna
                                           tower.
                                        3. The antenna height is varied from one meter to four meters above the
                                           ground to determine the maximum value of the field strength. Both
                                           horizontal and vertical polarizations of the antenna are set to make the
                                           measurement.
                                        4. For each suspected emission, the EUT was arranged to its worst case
                                           and then the antenna was tuned to heights from 1 meter to 4 meters
                                           and the rotatable table was turned from 0 degrees to 360 degrees to
                                           find the maximum reading.
                                        5. The test-receiver system was set to Peak Detect Function and
                                           Specified Bandwidth with Maximum Hold Mode.
                                        6. If the emission level of the EUT in peak mode was 10dB lower than the
                                           limit specified, then testing could be stopped and the peak values of the
                                           EUT would be reported. Otherwise the emissions that did not have
                                           10dB margin would be re-tested one by one using peak, quasi-peak or
                                           average method as specified and then reported in a data sheet.
       Test Instruments:                Refer to section 5.9 for details
       Test mode:                       Refer to section 5.3 for details
       Test results:                    Passed
       Remark:                          All of the observed value above 6GHz ware the niose floor , which were
                                        no recorded




Shenzhen Zhongjian Nanfang Testing Co., Ltd.                                            Project No.: CCISE1903094
No. B-C, 1/F., Building 2, Laodong No.2 Industrial Park, Xixiang Road,
Bao’an District, Shenzhen, Guangdong, China
Telephone: +86 (0) 755 2311 8282 Fax: +86 (0) 755 2311 6366                                            Page 12 of 30


CCIS                                                                                   Report No: CCISE190309401

Measurement Data:
Below 1GHz:

Product Name:                  Outdoor Smart UPS                   Product Model:                EPB41211

Test By:                       Carey                              Test mode:                     Full load mode

Test Frequency:                30 MHz ~ 1 GHz                      Polarization:                 Vertical

Test Voltage:                  AC 120/60Hz                         Environment:                  Temp: 24°C        Huni: 57%


      83 0I.evel (dBu\Vim)


      70
      60                                                                                             FCC PART15 CLAS$ A


      50

      40

      30


      20

      10


         030              50                    100                  200                             500               1000
                                                          Frequency (MHz)

                              ReadAntenna        Cable Preanp                 Limit       Over
                  Freq       Level Factor          Loss Factor      Level       Line     Limit Remark

                   NHz         dBu¥y    dB/m —        db _    dB dBu¥/n dBu¥/m                dB ~
     1          98. 142      50.39     12.04      1.97    29.54     34.86      53.50   —18.64     QP
     2         235.816       45.42     12.15      2.83    28.62     31.78      56.40   —24.62     QP
     3         375.939       42.91     14.97      3.09    28.68     32.29      56.40   —24.11     QP
     4         625.078       43.71     19.61      3.90    28.86     38.36      56.40   —18.04     QP
     5         T50.108       40.86     20.60      4.36    28.48     37.34      56.40   —19.06     P
     6         875.247       46.86     22.55      3.95    27.94     45.42      56.40   —10.98     QP


Remark:
1.   Final Level = Receiver Read level + Antenna Factor + Cable Loss — Preamplifier Factor.
2.   The emission levels of other frequencies are very lower than the limit and not show in test report.




Shenzhen Zhongjian Nanfang Testing Co., Ltd.                                                     Project No.: CCISE1903094
No. B—C, 1/F., Building 2, Laodong No.2 Industrial Park, Xixiang Road,
Bac‘an District, Shenzhen, Guangdong, China
Telephone: +86 (0) 755 2311 8282 Fax: +86 (0) 755 2311 6366                                                       Page 13 of 30


CCIS                                                                                      Report No: CCISE190309401


Product Name:                  Outdoor Smart UPS                       Product Model:              EPB41211

Test By:                       Carey                                   Test mode:                  Full load mode

Test Frequency:                30 MHz ~ 1 GHz                          Polarization:               Horizontal

Test Voltage:                  AC 120/60Hz                             Environment:                Temp: 24°C        Huni: 57%


     80Leve| (dBuVim)


     70

                                                                                                     FCC PART15 CLASS A
     60                                                                                                                r

     saf_ |_ L Lt
     40

     30

     20

     10


          30             50                     100                     200                          500                 1000
                                                             Frequency (MHz)

                               Readintenna       Cable Preamp                     Limit     Over
                      Freq    Level Factor        Loss Factor           Level      Line    Linmit Remark

               C       NEz     dBu¥y    dB/m            db _      dB dBu¥/m dBuT/n            dB
      1            149.486    49.72      8.58         2.51     29.22    31.59     53.50 —21.91 QP
      2            255.623    47.56    13.34          2.82     28.53    35.19     56.40 —21.21 QP
      3            375.939    43.22    15.08          3.09     28.68    32.71     56.40 —23.69 QP
      4            625.078    38.05    19.51      3.90         28.86    32.60     56.40 —23.80 QP
      5            T50.108    39.25    21.00      4.36         28.48    36.13     56.40 —20.27 qP
      6            875.247    48.00    21.81      3.95         27.94    45.82     56.40 —10.58 qP


Remark:
1. Final Level = Receiver Read level + Antenna Factor + Cable Loss — Preamplifier Factor.
2.   The emission levels of other frequencies are very lower than the limit and not show in test report.




Shenzhen Zhongjian Nanfang Testing Co., Ltd.                                                       Project No.: CCISE1903094
No. B—C, 1/F., Building 2, Laodong No.2 Industrial Park, Xixiang Road,
Bac‘an District, Shenzhen, Guangdong, China
Telephone: +86 (0) 755 2311 8282 Fax: +86 (0) 755 2311 6366                                                         Page 14 of 30


CCIS                                                                                    Report No: CCISE190309401

Above 1GHz:
Product Name:                 Outdoor Smart UPS                     Product Model:                EPB41211

Test By:                      Carey                                Test mode:                     Full load mode

Test Frequency:               1 GHz ~6 GHz                          Polarization:                 Vertical

Test Voltage:                 AC 120/60Hz                           Environment:                  Temp: 24°C          Huni: 57%


     100Level (dBuVim)


      90
      80                                                                                                FCC PART 15A (PK)

      70
                                                                                                        FCC PART 15A (AV)
      60

      50

      40                                                                                                                   5
                                                                                                        3

      30                                                           1

      20

      10

       01000     1200           1500               2000                                                        5000       6000
                                                          Frequency (MHz)

                           ReadAntenna        Cable Preamp                  Linmit      Over
                 Freq     Level Factor          Loss Factor       Level       Line     Limit Remark

                   NBz      dBuy       dB/m        dB        dB dBu¥/m dBu¥/m              dB
      1     2484.854      36.37       27.36     4.81      41.91    26.63     79.50   —52.87     Peak
      2     2484.854      30.28       27.36     4.81      41.91    20.54     59.50   —38.96     Average
      3     4377.203      356.60      30.38     6.67      41.95    30.70     79.50   —48.80     Peak
      4      4377.203     32.15       30.38     6.67      41.95    27.25     59.50   —32.25     Average
      5      §872.370     36.70       32.67     T.90      42.03    35.24     79.50   —44.26     Peak
      6      §872.370     31.85       32.67     7.90      42.03    30.39     59.50   —29.11     Average


Remark:
1. Final Level = Receiver Read level + Antenna Factor + Cable Loss — Preamplifier Factor.
2.    The emission levels of other frequencies are very lower than the limit and not show in test report.




Shenzhen Zhongjian Nanfang Testing Co., Ltd.                                                      Project No.: CCISE1903094
No. B—C, 1/F., Building 2, Laodong No.2 Industrial Park, Xixiang Road,
Bac‘an District, Shenzhen, Guangdong, China
Telephone: +86 (0) 755 2311 8282 Fax: +86 (0) 755 2311 6366                                                        Page 15 of 30


CCIS                                                                                   Report No: CCISE190309401



Product Name:                 Outdoor Smart UPS                    Product Model:                  EPB41211

Test By:                      Carey                               Test mode:                       Full load mode

Test Frequency:               1 GHz ~ 6 GHz                        Polarization:                   Horizontal

Test Voltage:                 AC 120/60Hz                          Environment:                    Temp: 24°C          Huni: 57%


     100 Level (dBu\Vim)


      90
      80                                                                                               FCC PART 15A (PK)

      70
      eo                                                                                               FCC PART 15A (AV)

      50

      40                                                                                                                   z

      30                                                                     1                 a
      ZOW,WMMWWWW
      10

       01000     1200           1500              2000                                                          5000      6000
                                                         Frequency (MHz)

                           Read&ntenna       Cable Preamp                Limit       Over
                 Freq      Level Factor       Loss Factor       Level      Line     Linmit Remark

           C      NHz       dbu¥y     db/m       dB       dB dBu¥/m dBu¥/n              dB              C
      1.    20936.411      35.32    28.37     5.29    41.56     27.43     79.50    —52.07    Peak
      20    2935.411       31.83    28.37     5.29    41.55     23.94     59.50    —35.56    Average
      3      3924.004      34.91    30.06     6.10    41.80     29.27     79.50    —50.23    Peak
      4      3924.004      30.78    30.06     6.10    41.80     25.14     59.50    —34.36    Average
      5      5819.996      35.65    32.66     7.89    42.02     34.18     79.50    —45.32    Peak
      6      5819.996      31.50    32.66     T.89    42.02     30.03     59.50    —29.47    Average



Remark:
1. Final Level = Receiver Read level + Antenna Factor + Cable Loss — Preamplifier Factor.
2.   The emission levels of other frequencies are very lower than the limit and not show in test report.




Shenzhen Zhongjian Nanfang Testing Co., Ltd.                                                       Project No.: CCISE1903094
No. B—C, 1/F., Building 2, Laodong No.2 Industrial Park, Xixiang Road,
Bac‘an District, Shenzhen, Guangdong, China
Telephone: +86 (0) 755 2311 8282 Fax: +86 (0) 755 2311 6366                                                         Page 16 of 30



Document Created: 2019-04-25 11:32:12
Document Modified: 2019-04-25 11:32:12

© 2024 FCC.report
This site is not affiliated with or endorsed by the FCC