1. Description
The Smart Smoke Sensor is a wireless, battery-powered sensor to detect
smoke. It can be used in commercial, industrial or residential buildings. Since
there is nowire needed, it can be easily and simply installed on walls and
ceilings.
The sensor has a photoelectric sensor embedded to sense the smoke a loud
buzzer to generate sound alarm.
The sensor connects to Sigfox network. With this linkage, you can receive
notification or check its status on Sigfox network when events occur. Therefore,
you will be able to response by actions instantly toprotect your home and
property.
With SensingTEKcloud system, you can set your desired triggerevent action to
control the other SensingTEK Smart Peripheral when the smoke isdetected.
For example, to trigger alarm or siren.


2. Features
• Photoelectric smoke alarm
• Removable smoke chamber for easy maintenance
• Automatic calibration and self-test
• Low battery and malfunction are under full supervision
• Manual test button helps to verify battery status and alarm operation
• Aesthetically appealing professional detector design
• Notification sent to smart phone or table when smoke detector alarm
• Easy to install, move and maintain
• Alarm mode - SensingTEK cloud system will link smoke detector with other
devices suchas motion sensor. The smoke detector will alarm when motion
sensor detectmoving objects


                                                    LED indicator
                                                    Test Button




3. Specification
Item                             Description

RF Module                        902.14MHz
Battery Power                    Rating Voltage: DC 3V for Lithium
                                 battery
Battery type                     CR123A

Smoke Sensitivity & Alarm        1.31%/ft ~ 2.28%/ft ;Temporal Three
Pattern UL217                    Pattern
Smoke Sensitivity & Alarm        0.105 dB/m ~ 0.156dB/m ;Temporal
Pattern EN 14604                 Three Pattern
Smoke Sensitivity UL268          Recognized component
                                 Standby: MAX 15uA/SD360, MAX
                                 10uA/RF module
Current drain                    Start: MAX 3.5mA
                                 Alarm: MAX 100 mA/SD360, MAX
                                 60mA/RF module
                                 Action button for Pairing, self test
I/O                              LED indicator for sending, alarm, and
                                 warning
indoor/Outdoor                   indoor
Sigfox      Transmission range   25km for open space
Operating Temperature            0 ~ 40ºC
Operating Humidity               10% ~ 85% RH
Self-test                        yes
Dimension                        120(Diameter) x 53 mm


4. LED status



`                      LED status
Sigfoxnetwork status   Blue LED
                       1. Blinking : Power ON
                       2. LED OFF: Standby Mode
                       3. Flash once: Send alarm signal.
Test mode              After pressing test button for around
                       1 second, the
                       buzzer sounds and Red LED flashes
                       continuously
Smoke Alarm Mode       When smoke detector senses
                       smoke, the buzzersounds an audible
                       alarm with 3 beeps, pause 1.5
                       seconds, then 3 beeps.The Red LED
                       will flash continuously and rapidly
Low battery            Buzzer chirps once in 43 seconds
                       with Yellow LED
                       flashing
Tamper                 When bracket is removed from
                       detector, the YellowLED is steadily
                       on and buzzer sounds temporarily
                       until the detector is mounted back to
                       the bracket.
                       The detector will be also alarmed if
                       the detector is
                       not mounted in the bracket within 3
                       minutes untilthe bracket is mounted


5. Accessories
• One CR123A battery
  • Two screws
  • Two plastic wall plugs

6. System Required
     • iOS - iOS 8.0 and above Ready devices.
     • Android - Android 4.3 above Ready devices



7.
• Before starting to use Dexatek Smart Smoke Sensor, please make sure you
   haveΣCentral/Smart gateway and ΣCasa App installed. If you don’t have
   ΣCasa App onyour smart phone, please download from Google Play for
   Android phone or Applestore for iPhone.



 • Installing your Smart Smoke Sensor
(1) At the place where you are going to install your Smart Smoke Sensor, draw a
   horizontalline six inches long
(2) Remove the mounting bracket from your unit by rotating it counterclockwise
(3) Place the bracket so that the two longest hold slots are aligned on the line. In each
   ofkeyhole slots, drawing a mark to locate a mounting plug and screw
(4) Remove the bracket
(5) Using a 3/16-inch (5mm) drill bit, drills two holes at the marks and insert plastic
   wallplugs. Put the Smart Smoke Sensor away from plastic dust on it when you drill
   holds formounting
(6) Using the two screws and plastic wall plugs (all supplied), attach the bracket to the
     wall
(7) Line up the slot of the bracket and the Smart Smoke Sensor. Push the sensor onto
themounting bracket on turn it clockwise to fix it into the place. Pull onward on the
SmartSmoke Sensor to make sure it is securely attached to the mounting bracket


CAUTION: This smoke alarm comes with cover latches that will prevent the
smokealarm cover from closing if battery is not installed. This tells you that the
smoke alarmwill not work until a new battery is properly installed.
NOTE: alarm horn will beep once after the detector is installed with battery and
mounted with bracket 2~4 seconds. This means the smoke alarm is working
normallyand also indicates that the battery is positioned properly. Close cover,
and then pressthe test button, holding it down for about 3 seconds until the
horn sounds. The hornshould sound a loud, pulsating alarm. This means the
unit is working properly.
• Battery Installation


FCC Statement
Changes or modifications not expressly approved by the party responsible for
compliance could void the user's authority to operate the equipment.
This equipment has been tested and found to comply with the limits for a Class
B digital device, pursuant to Part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates uses and can radiate radio
frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and
on, the user is encouraged to try to correct the interference by one or more of
the following measures:
-- Reorient or relocate the receiving antenna.
-- Increase the separation between the equipment and receiver.
-- Connect the equipment into an outlet on a circuit different from that to which
the receiver is connected.
-- Consult the dealer or an experienced radio/TV technician for help
This device complies with part 15 of the FCC rules. Operation is subject to the
following two conditions (1)this device may not cause harmful interference,
and (2) this device must accept any interference received, including
interference that may cause undesired operation.



Document Created: 2018-06-25 15:49:20
Document Modified: 2018-06-25 15:49:20

© 2024 FCC.report
This site is not affiliated with or endorsed by the FCC